Ingangsdatum: 01-07-2009 
              
                
                  
                    
                      | The purpose
												of this section is to ensure a consistent level of
												structural fire protection. The principles of the
												section aim to achieve a level of fire protection
												compatible with the requirements of SOLAS for
												passenger ships carrying up to 36 passengers. These
												have been adapted where appropriate to fit the
												general yacht design philosophy. Much emphasis is
												placed on the provision of sprinkler/mist systems as
												trade-off for certain
									aspects. | 
                  
                
  
                
                
              
                14B.1 Definitions
               
              Terms used in this section should have the same meaning as defined in
								SOLAS, except as defined in Section 14.1 and as follows: 
              "Not readily ignitable" means that the surface thus described will
								not continue to burn for more than 20 seconds after removal of a
								suitable impinging test flame; 
              
                
                14B.2 Table 14B.2 is a guide to
								the major requirements of this Section. The Table is intended as a
								quick reference to the requirements and is not to be used in
								isolation when designing the fire safety arrangements. 
              
                Table 14B.2
               
              All vessels should comply with the following: - 
              
                
                  
                    
                      | Form of construction (see 14B.2.1)      | Steel or equivalent, or
												alternative forms of construction may be accepted
												subject to requirements. | 
                    
                      | Passive fire protection (see 14B.2.1 to
												14B.2.7) | See
												Tables 1 and 2 | 
                    
                      | Means of escape (see 14B.2.12).  |    2 (two)2 (two)
 | 
                    
                      | Fixed fire detection system (see 14B.2.15).  Fire extinguishing arrangements in Category ‘A’
												machinery spaces (see 15B)  | 
                          Fitted in machinery spaces.  Fitted in service spaces, control stations and
												accommodation spaces. As per SOLAS II-2/10.5 | 
                    
                      | Automatic
												sprinkler system or equivalent (see 14B.2.14) | Fitted in all vessels | 
                  
                
                
                14B.2.1 Structure
               
              
                Purpose
               
              The purpose of this section is to contain a fire in the space of
								origin. For this purpose, the following functional requirements
								should be met: 
              
                - the ship should be subdivided by thermal and structural
									boundaries; 
- thermal insulation of boundaries should have due regard to the
									fire risk of the space and adjacent spaces; 
- the fire integrity of the divisions should be maintained at
									openings and penetrations.
                14B.2.2.1 The hull, superstructures, structural
								bulkheads, decks and deckhouses should be constructed of steel or
								other equivalent material.  
              
                14B.2.2.2 However, in cases where any part of the
								structure is of aluminium alloy, the following should apply: - 
              
                - Insulation of aluminium alloy components of "A" or "B" class
									divisions, except structure which, in the opinion of the
									Administration, is non-load-bearing, should be such that the
									temperature of the structural core does not rise more than 200°C
									above the ambient temperature at any time during the applicable
									fire exposure to the standard fire test.  This insulation is to
									be applied on all sides except for the upper sides of decks and
									the outside of the vessel
 
 
- Special attention should be given to the insulation of aluminium
									alloy components of columns, stanchions and other structural
									members required to support lifeboat and liferaft stowage,
									launching and embarkation areas, and "A" and "B" class divisions
									to ensure that for members:
 (a) supporting
									lifeboat and liferaft areas and "A" class divisions, the
									temperature rise limitation specified in .1 above should apply
									at the end of one hour; and
 
 
 (b) supporting "B" class divisions, the
									temperature rise limitation specified in .1 above should apply
									at the end of half an hour.
 
 
- Aluminium alloy components of divisions that are required to be
									equivalent to steel (identified by an * in tables 1 and 2)
									should be insulated with 25mm of mineral wool approved for use
									in A class divisions or with an equivalent insulation acceptable
									to the administration.
                14B.2.2.3 For composite structures, the insulation
								is to be such that the temperature of the laminate does not rise
								more than the minimum temperature of deflection under load of the
								resin at any time during the specified fire exposure. The
								temperature of deflection under load is to be determined in
								accordance with the requirements of a recognised international
								standard.  This insulation is to be applied on all sides except for
								the upper sides of decks and the outside of the vessel. 
              
                - Special attention should be given to the insulation of composite
									components of columns, stanchions and other structural members
									required to support lifeboat and liferaft stowage, launching and
									embarkation areas, and "A" and "B" class divisions to ensure
									that for members:
 (a) supporting lifeboat and
									liferaft areas and "A" class divisions, the temperature rise
									limitation specified in .1 above should apply at the end of one
									hour; and
 
 (b) supporting "B"
									class divisions, the temperature rise limitation specified in .1
									above should apply at the end of half an hour.
                
Special attention is to be given to the fixing of
								fire door frames in bulkheads constructed of materials other than
								steel. Measures are to be taken to ensure that the temperature of
								the fixings when exposed to fire does not exceed the temperature at
								which the bulkhead itself looses strength. 
              
                14B.2.2.4 Crowns and casings of a machinery space of
								category A should be A60 divisions and openings therein, if any,
								should be suitably arranged and protected to prevent the spread of
								fire. 
              
                14B.2.2.5 For structures in contact with sea-water,
								the required insulation should extend to at least 300 mm below the
								lightest waterline. 
              
                14B.2.2.6 Fire divisions using steel equivalent, or
								alternative forms of construction may be accepted if it can be
								demonstrated that the material by itself, or due to non-combustible
								insulation provided, has the fire resistance properties equivalent
								to the A or B class standard required. 
              
                14B.2.2.7 Insulation required by 14B.2.2.6 is to be
								such that the temperature of the structural core does not rise above
								the point at which the structure would begin to lose its strength at
								any time during the applicable exposure to the standard fire test.
								For 'A' Class divisions, the applicable exposure is 60 minutes, and
								for 'B' Class divisions, the applicable exposure is 30 minutes. 
                
              
                14B.2.3 Main vertical zones and horizontal zones
               
              
                14B.2.3.1 Hull, superstructure and deckhouses in way
								of accommodation and service spaces should be subdivided into main
								vertical zones by "A" class divisions.  These divisions should have
								insulation values in accordance with tables 1 and 2.  
              
                14B.2.3.2 As far as practicable, the bulkheads
								forming the boundaries of the main vertical zones above the bulkhead
								deck should be in line with watertight subdivision bulkheads
								situated immediately below the bulkhead deck. The length and width
								of main vertical zones may be extended to a maximum of 48 m in order
								to bring the ends of main vertical zones to coincide with watertight
								subdivision bulkheads or in order to accommodate a large public
								space extending for the whole length of the main vertical zone
								provided that the total area of the main vertical zone is not
								greater than 800 m2 on any deck. The length or width of a main
								vertical zone is the maximum distance between the furthermost points
								of the bulkheads bounding it. 
              
                14B.2.3.3 Such bulkheads should extend from deck to
								deck and to the shell or other boundaries. 
              
                14B.2.3.4 When a main vertical zone is subdivided by
								"A" class divisions for the purpose of providing an appropriate
								barrier between spaces protected and not protected by a sprinkler
								system, the divisions should be insulated in accordance with the
								fire insulation and integrity values given in tables 1 and 2. 
              
                
  
              
                14B.2.4 Bulkheads within a main vertical zone
               
              
                14B.2.4.1 All bulkheads within accommodation and
								service spaces which are not required to be "A" class divisions
								should be at least "B" class or "C" class divisions as prescribed in
								the tables 1 and 2 . 
              
                14B.2.4.2 All such divisions may be faced with
								combustible materials 
              
                14B.2.4.3 All corridor bulkheads, where not required
								to be "A" class should be "B" class divisions which should extend
								from deck to deck except: 
              
                - when continuous "B" class ceilings or linings are fitted on both
									sides of the bulkhead, the portion of the bulkhead behind the
									continuous ceilings or lining should be of material which, in
									thickness and composition, is acceptable in the construction of
									"B" class divisions but which should be required to meet "B"
									class integrity standards only in so far as is reasonable and
									practical in the opinion of the Administration;
 
 
- the corridor bulkheads of "B" class materials may terminate at a
									ceiling in the corridor provided such a ceiling is of material
									which, in thickness and composition, is acceptable in the
									construction of "B" class divisions. All doors and frames in
									such bulkheads should be so constructed and erected to provide a
									“B” class standard.
                14B.2.4.4 All bulkheads required to be "B" class
								divisions, except corridor bulkheads, should extend from deck to
								deck and to the shell or other boundaries unless continuous "B"
								class ceilings or linings are fitted on both sides of the bulkhead,
								in which case the bulkhead may terminate at the continuous ceiling
								or lining. 
              
                
                14B.2.5 Fire integrity of bulkheads and decks
               
              
                14B.2.5.1 In addition to complying with the specific
								provisions for fire integrity of bulkheads and decks mentioned
								elsewhere in this section, the minimum fire integrity of bulkheads
								and decks should be as prescribed in tables 1 and 2. 
              
                14B.2.5.2 The following requirements should govern
								application of the tables: 
              
                - Tables 1 and 2 should apply respectively to the bulkheads and
									decks separating adjacent spaces.
 
 
- For determining the appropriate fire integrity standards to be
									applied to divisions between adjacent spaces, such spaces are
									classified according to their fire risk as shown in categories
									(1) to (9) below.  The title of each category is intended to be
									typical rather than restrictive.  The number in parentheses
									preceding each category refers to the applicable column or row
									in the tables.
                (1) Control stations
               
              
                - Spaces containing emergency sources of power and lighting. 
- Wheelhouse and chartroom. 
- Spaces containing the vessel's radio equipment. 
- Fire-extinguishing rooms. 
- Fire control rooms and fire-recording stations 
- Control room for propulsion machinery when located outside the
									machinery space. 
- Spaces containing centralized fire alarm equipment.
 
 
                (2) Corridors and lobbies
               
              
              
                (3) Accommodation spaces
               
              
                - Cabins, dining rooms, lounges, offices, pantries containing no
									cooking appliances (other than equipment such as microwave
									cookers and toasters), and similar spaces.
                (4) Stairways
               
              
                - Interior stairways, lifts and escalators (other than those
									wholly contained within the machinery space(s)) and enclosures
									thereto. 
- In this connection, a stairway which is enclosed only at one
									level should be regarded as part of the space from which it is
									not separated by a fire door.
 
 
                (5) Service spaces (low risk)
               
              
                - Lockers and store-rooms not having provisions for the storage of
									flammable liquids and having areas less than 4m², and drying
									rooms and laundries.
 
 
                (6) Machinery spaces of category A,
               
              
              
                
                (7) Other machinery spaces
               
              
                - Spaces so defined, excluding machinery spaces of category A. 
- Sprinkler, drencher or fire pump spaces.
 
                
                (8) Service spaces (high risk)
               
              
              
              
                - Galleys, pantries containing cooking appliances, paint and
									lamp rooms, lockers and store-rooms having areas of 4m² or more,
									spaces for the storage of flammable liquids, workshops other
									than those forming part of the machinery spaces, and spaces
									containing vehicles or craft with fuel in their tanks, or
									lockers storing such fuels storage lockers for gaseous fuels for
									domestic purposes.  
                (9) Open decks
               
              
                - Open deck spaces and enclosed promenades having no fire risk.
									Air spaces (the space outside superstructures and
										deckhouses).
 
                14B.2.5.3 Continuous "B" class ceilings or linings,
								in association with the relevant decks or bulkheads, may be accepted
								as contributing, wholly or in part, to the required insulation and
								integrity of a division. 
              
                14B.2.5.4 External boundaries which are required to
								be of steel or other equivalent material may be pierced for the
								fitting of windows and portlights provided that there is no
								requirement for such boundaries to have "A" class integrity
								elsewhere in this section.  Similarly, in such boundaries which are
								not required to have "A" class integrity, doors may be of
								combustible materials, substantially constructed. 
              
                Table 1 - Fire integrity of bulkheads separating adjacent
									spaces
               
              
                
                
                  
                    
                      | Spaces | (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | 
                    
                      | Control
												stations (1) | A-0c | A-0 | A-60 | A-0 | A-15 | A-60 | A-15 | A-60 | * | 
                    
                      | Corridors and
												lobbies  (2) |  | Cd | B-0d | A-0a B-0d
 | B-0d | A-60 | A-0 | A-0 | * | 
                    
                      | Accommodation
												spaces  (3) |  |  | Cd | A-0a B-0d
 | B-0d | A-60 | A-0 | A-0 | * | 
                    
                      | Stairways (4) |  |  |  | A-0a B-0d
 | A-0a B-0d
 | A-60 | A-0 | A-0 | 
                          **
 | 
                    
                      | Service
												spaces  (low risk) (5) |  |  |  |  | Cd | A-60 | A-0 | A-0 | * | 
                    
                      | Machinery spaces of
												category A  (6) |  |  |  |  |  | * | A-0 | A-60 | * | 
                    
                      | Other machinery
												spaces (7) |  |  |  |  |  |  | A-0b | A-0 | * | 
                    
                      | Service spaces
												(high risk)  (8) |  |  |  |  |  |  |  | A-0b | * | 
                    
                      | Open decks
												 (9) |  |  |  |  |  |  |  |  |  | 
                  
                
  
                
                
                
                
              
                
  
                
                
                
              
                Table 2 - Fire integrity of decks separating adjacent
									spaces
               
              
                
                  
                    
                      | Spaces | (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | 
                    
                      | Control
												stations (1) | A-0 | A-0 | A-0 | A-0 | A-0 | A-60 | A-0 | A-0 | * | 
                    
                      | Corridors and
												lobbies  (2) | A-0 | * | * | A-0 | * | A-60 | A-0 | A-0 | * | 
                    
                      | Accommodation
												spaces  (3) | A-60 | A-0 | * | A-0 | * | A-60 | A-0 | A-0 | * | 
                    
                      | Stairways (4) | A-0 | A-0 | A-0 | * | A-0 | A-60 | A-0 | A-0 | *  | 
                    
                      | Service spaces 
												(low risk) (5) | A-15 | A-0 | A-0 | A-0 | * | A-60 | A-0 | A-0 | * | 
                    
                      | Machinery
												spaces of category A  (6) | A-60 | A-60 | A-60 | A-60 | A-60 | * | A-60e | A-60 | * | 
                    
                      | Other machinery
												spaces (7) | A-15 | A-0 | A-0 | A-0 | A-0 | A-0 | * | A-0 | * | 
                    
                      | Service spaces
												(high risk)  (8) | A-60 | A-0 | A-0 | A-0 | A-0 | A-60 | A-0 | A-0 | * | 
                    
                      | Open decks
												 (9) | * | * | * | * | * | * | * | * | - | 
                  
                
  
                
                
                
                
                
                
                
              Notes: To be applied to both tables 1 and 2, as appropriate. 
              
                
                  
                    
                      | a | For clarification on which
												applies, see 14B.2.4 and 14B.2.6. | 
                    
                      | b | Where spaces are of the same
												numerical category and subscript b appears, a
												bulkhead or deck of the rating shown in the tables
												is only required when the adjacent spaces are for a
												different purpose, e.g in category (9).  a galley
												next to a galley does not require a bulkhead but a
												galley next to a paint room requires an "A-0"
												bulkhead. | 
                    
                      | c | Bulkheads separating the
												wheelhouse and chartroom from each other may be
												"B-0" rating. | 
                    
                      | d | For the application of
												14B.2.3.1, "B-O" and "C", where appearing in table
												1, should be read as "A-0". | 
                    
                      | e | Fire insulation need not be
												fitted if the machinery space in category (7), in
												the opinion of the Administration, has little or no
												fire risk. | 
                    
                      | * | Where an asterisk appears in
												the tables, the division is required to be of steel
												or other equivalent material but is not required to
												be of "A" class standard. | 
                  
                
                
  
                
                
                
                
                
                
                
              For the application of 14B.2.3.1 an asterisk, where appearing in
								table 2, except for category (9), should be read as "A-0". 
                
              
                14B.2.6 Protection of stairways and lifts in accommodation
									and service spaces
               
              
                14B.2.6.1 A stairway should be of steel frame
								construction except where the Administration sanctions the use of
								other equivalent material, and should be within enclosures formed of
								"A" class divisions, with positive means of closure at all openings,
								except that: 
              
                - an isolated stairway which penetrates a single deck only may be
									protected at one level only by at least "B" class divisions and
									self-closing door(s); and 
- stairways may be fitted in the open in a public space, provided
									they lie wholly within such public space.
                14B.2.6.2 A stairway enclosure should have direct
								communication with the corridors and be of sufficient area to
								prevent congestion, having in view the number of persons likely to
								use them in an emergency. In so far as is practical, stairway
								enclosures should not give direct access to galleys, machinery
								spaces, service lockers, or other enclosed spaces containing
								combustibles in which a fire is likely to originate. 
              
                14B.2.6.3 A lift trunk should be so fitted to
								prevent the passage of flame from one 'tween-deck to another and
								should be provided with means of closing to permit the control of
								draught and smoke. 
                
              
                14B.2.7 Openings in "A" class divisions
               
              
                14B.2.7.1 Except for hatches between store and
								baggage spaces, and between such spaces and the weather decks, all
								openings should be provided with permanently attached means of
								closing which should be at least as effective for resisting fires as
								the divisions in which they are fitted. 
              
                14B.2.7.2 The construction of all doors and door
								frames in "A" class divisions, with the means of securing them when
								closed, should provide resistance to fire as well as the passage of
								smoke and flame, as far as practical, equivalent to that of the
								bulkheads in which the doors are situated.  Such doors and door
								frames should be constructed of steel or other equivalent material. 
								Steel watertight doors need not be insulated. 
              
                14B.2.7.3 It should be possible for each door to be
								opened and closed from each side of the bulkhead by one person
								only. 
              
                14B.2.7.4 Fire doors in main vertical zone
								bulkheads, galley boundaries and stairway enclosures other than
								power-operated watertight doors and those which are normally locked,
								should satisfy the following requirements: 
              
                
                  
                    
                      | (a) | the doors
												should be self-closing and be capable of closing
												with an angle of inclination of up to 3.5º opposing
												closure; 
 | 
                    
                      | (b) | the approximate time of
												closure for hinged fire doors should be no more than
												40 seconds and no less than 10 seconds from the
												beginning of their movement with the ship in the
												upright position. The approximate uniform rate of
												closure for sliding doors should be of no more than
												0.2 m/s and no less than 0.1 m/s with the ship in
												the upright position; 
 | 
                    
                      | (c) | the
												doors, except those for emergency escape trunks,
												should be capable of remote release from the
												continuously manned central control station, either
												simultaneously or in groups and should also be
												capable of release, individually, from a position at
												the door. Release switches should have an on-off
												function to prevent automatic resetting of the
												system; 
 | 
                    
                      | (d) | hold-back hooks not subject
												to central control station release are prohibited; 
 | 
                    
                      | (e)  | a door
												closed remotely from the central control station
												should be capable of being re-opened from both sides
												of the door by local control. After such local
												opening, the door should automatically close
												again; 
 | 
                    
                      | (f) | indication must be provided
												at the fire door indicator panel in the continuously
												manned central control station whether each door is
												closed; 
 | 
                    
                      | (g) | the release mechanism should
												be so designed that the door will automatically
												close in the event of disruption of the control
												system or central power supply; 
 | 
                    
                      | (h) | local power accumulators for power-operated doors
												should be provided in the immediate vicinity of the
												doors to enable the doors to be operated after
												disruption of the control system or central power
												supply at least ten times (fully opened and closed)
												using the local controls; 
 | 
                    
                      | (i) | disruption of
												the control system or central power supply at one
												door should not impair the safe functioning of the
												other doors 
 | 
                    
                      | (j) | remote-released sliding or
												power-operated doors should be equipped with an
												alarm that sounds at least 5 s but no more than 10s
												after the door being released from the central
												control station and before the door begins to move
												and continues sounding until the door is completely
												closed; 
 | 
                    
                      | (k) | a door designed to re-open
												upon contacting an object in its path should re-open
												not more than 1 m from the point of contact 
 | 
                    
                      | (l) | double-leaf doors equipped with a latch
												necessary for their fire integrity should have a
												latch that is automatically activated by the
												operation of the doors when released by the
												system 
 | 
                    
                      | (m) | the components of the local
												control system should be accessible for maintenance
												and adjusting; 
 | 
                    
                      | (n) | power-operated doors should
												be provided with a control system of an approved
												type which should be able to operate in case of fire
												and be in accordance with the Fire Test Procedures
												Code. This system should satisfy the following
												requirements: 
 | 
                    
                      |  | 
                          the control system should be able to operate
												the door at the temperature of at least 200°C for
												at least 60 min, served by the power supply;
the power supply for all other doors not
												subject to fire should not be impaired; and
at temperatures exceeding 200°C the
												control system should be automatically isolated
												from the power supply and should be capable of
												keeping the door closed up to at least
												945°C. | 
                  
                
  
                
                
                
                
                
                
                
                
                
                
                
                
                 
                
               
                      
                
                
                 
                 
                 
   
·   
              ·  
              
                14B.2.7.5 Where 'A' Class divisions are penetrated
								for the passage of electric cables, pipes, trunks, ducts, etc., or
								for girders, beams or other structural members, arrangements are to
								be made to ensure that the fire resistance is not impaired. 
                
              
                
                14B.2.8 Openings in "B" class divisions
               
              
                14B.2.8.1 Doors and door frames in "B" class
								divisions and means of securing them should provide a method of
								closure which should have resistance to fire as far as practical
								equivalent to that of the divisions except that a ventilation
								opening may be permitted in the lower portion of such doors.  When
								such an opening is in or under a door the total net area of the
								opening(s) should not exceed 0.05m².  When such an opening is cut in
								a door it should be fitted with a grill made of non-combustible
								material.  Doors should be non-combustible or of substantial
								construction. 
              
                14B.2.8.2 Where 'B' Class divisions are penetrated
								for the passage of electric cables, pipes, trunks, ducts, etc., or
								for the fitting of ventilation terminals, lighting fixtures and
								similar devices, arrangements are to be made to ensure that the fire
								resistance is not impaired. 
                
              
                
                14B.2.9 Windows and portlights (Also see 5.4 and
									5.5)
               
              
                14B.2.9.1 All windows and portlights in bulkheads
								within accommodation spaces, service spaces and control stations
								should be so constructed to preserve the integrity requirements of
								the type of bulkheads in which they are fitted. 
              
                14B.2.9.2 Glass is not to be installed as an
								interior main vertical zone, stairway enclosure bulkhead, or within
								machinery space boundaries. 
                
              
                
                14B.2.10 Details of construction
               
              
                14B.2.10.1 In accommodation and service spaces,
								control stations, corridors and stairways: 
              
                - air spaces enclosed behind ceilings, panelling or linings should
									be suitably divided by close-fitting draught stops not more than
									14m apart; and
 
 
- in the vertical direction, enclosed air spaces, including those
									behind linings of stairways, trunks, etc. should be closed at
									each deck.
                14B.2.10.2 The draught stops are to be
								non-combustible and are to form a continuation above the ceiling of
								the bulkhead below or the other side of the panelling or lining to
								the bulkhead, as far as possible. 
              
                14B.2.10.3 Where the structure or 'A' Class
								divisions are required to be insulated, it is to be ensured that the
								heat from a fire is not transmitted through the intersections and
								terminal points of the divisions or penetrations to uninsulated
								boundaries. Where the insulation installed does not achieve this,
								arrangements are to be made to prevent this heat transmission by
								insulating the horizontal and vertical boundaries or penetrations
								for a distance of 450 mm. 
              
                14B.2.10.4 Without impairing the efficiency of the
								fire protection, the construction of ceilings and bulkheads should
								allow a fire patrol to detect any smoke originating in concealed and
								inaccessible places, except where there is no risk of fire
								originating in such places. 
              
                14B.2.10.5 When gaseous fuel is used for domestic
								purposes, the arrangements for the storage, distribution and
								utilisation of the fuel should be such that, having regard to the
								hazards of fire and explosion which the use of such fuel may entail,
								the safety of the vessel and the persons onboard are preserved. 
               In particular, open flame gas appliances provided for cooking,
								heating or any other purposes, should comply with the requirements
								of EC directive 90/396/EEC or equivalent and, the installation of
								open flame gas appliances should comply with the appropriate
								provisions of Section 14A.5 
                
              
                
                14B.2.11 Restricted use of combustible materials
               
              
                14B.2.11.1 Except in spaces protected by an
								automatic sprinkler system and fully addressable fire detection
								system in accordance with 14B.2.14, all linings, grounds, and
								ceilings should be of non-combustible materials 
              
                14B.2.11.2 The use of combustible materials is to be
								kept to a minimum. Insulation materials should be
								non-combustible. 
              
                14B.2.11.3 The following surfaces should be low
								flame spread: 
              
                - exposed surfaces in corridors and stairway enclosures, and of
									bulkheads, wall and ceiling linings in all service spaces and
									control stations; and
 
 
- concealed or inaccessible spaces in accommodation, service
									spaces and control stations.
 
 
 As an alternative to .1 and .2 above,
									these spaces may contain surfaces that are not low flame spread,
									provided
 
 
- adequate barriers of low flame spread surfaces are arranged to
									restrict the spread of flame areas at distances not greater than
									5m, or
 
 
- these spaces are protected by an automatic sprinkler system and
									fully addressable fire detection system in accordance with
										14B.2.14.
 14B.2.11.4 Pipes penetrating 'A'
									or 'B' Class divisions are to be of approved materials having
									regard to the temperature such divisions are required to
									withstand.
                14B.2.11.5 Pipes conveying oil or combustible
								liquids through accommodation and service spaces are to be of
								approved materials having regard to the fire risk. 
              
                14B.2.11.6 Materials readily rendered ineffective by
								heat are not to be used for overboard scuppers, sanitary discharges,
								and other outlets which are close to the waterline and where the
								failure of the material in the event of fire would give rise to the
								danger of flooding. 
              
                14B.2.11.7 Furniture in the corridors and escape
								routes should be of a type and quantity not likely to obstruct
								access. Additionally, furniture along escape routes should be
								secured in place to prevent shifting if the vessel rolls or
								lists. 
              14B.2.11.8 Primary deck coverings within accommodation
									spaces, service spaces and control stations are to be
								of a type which will not readily ignite, or give rise to toxic or
								explosive hazards at elevated temperatures. Reference is also to be
								made to the IMO FTP Code, Annex 1, Parts 2 and 6. 
              
                14B.2.11.9 Vapour barriers and adhesives used in
								conjunction with insulation, as well as insulation of pipe fittings
								for cold service systems need not be non-combustible, but they
								should be kept to the minimum quantity practicable and their exposed
								surfaces should have low flame spread characteristics. 
              
                14B.2.11.10 Except when a fully addressable fire
								detection system is fitted,  upholstery composites (fabric in
								association with any backing or padding material) used throughout
								the vessel should be approved in accordance with the IMO FTP Code,
								Annex 1, Part 8 or an equivalent standard acceptable to the
								administration. 
              
                14B.2.11.11 Except when a fully addressable fire
								detection system is fitted bedding components should be approved in
								accordance with the IMO FTP Code, Annex 1, Part 9 or an equivalent
								standard acceptable to the administration 
              
                14B.2.11.12 Except when a fully addressable fire
								detection system is fitted Suspended textile materials such as
								curtains and drapes should be approved in accordance with the IMO
								FTP Code, Annex 1, Part 7, or an equivalent standard acceptable to
								the administration 
              
                14B.2.11.13 Upholstery, bedding components and
								suspended textiles required to comply with the IMO FTP code or an
								equivalent standard are to be clearly labelled by the manufacturer
								stating the standard that they meet and any washing or cleaning
								instructions needed to maintain their fire resistance. These labels
								are not to be removed. 
              
                14B.2.11.14 In spaces where penetration of oil
								products is possible, the surface of insulation is to be impervious
								to oil or oil vapours. Insulation boundaries are to be arranged to
								avoid immersion in oil spillages so far as is practicable. 
                
              
                
                14B.2.12 Means of escape
               
              
                 Purpose
               
               The purpose of this section is to provide means of escape so that
								persons onboard can safely and swiftly escape to the lifeboat and
								liferaft embarkation deck. For this purpose, the following
								functional requirements should be met: 
              
                - safe escape routes should be provided; 
- escape routes should be maintained in a safe condition, clear of
									obstacles; and 
- additional aids for escape should be provided as necessary to
									ensure accessibility, clear marking, and adequate design for
									emergency situations.
                14B.2.12.1 Stairways and ladders should be arranged
								to provide ready means of escape to the lifeboat and liferaft
								embarkation deck from all guest and crew accommodation spaces and
								service spaces in which the crew are normally employed, other than
								machinery spaces. In particular, the following provisions should be
								complied with: 
              
                - 
                  Below the bulkhead deck two means of escape, at least one
									of which should be independent of watertight doors, should be
									provided from each watertight compartment, main vertical zone or
									similarly restricted group of spaces.  Exceptionally one of the
									means of escape may be dispensed with, due regard being paid to
									the nature and location of spaces and to the number of persons
									who might normally be accommodated or employed there.
 
 
- 
                  Above the bulkhead deck, there are to be at least two
									means of escape from each vertical fire zone or similarly
									restricted spaces or group of spaces, at least one of which is
									to give access to an readily accessible escape which will
									provide continuous fire shelter from the level of its origin to
									the appropriate survival craft embarkation deck
 
 
- Within each main vertical zone there should be at least one
									readily accessible enclosed stairway providing continuous fire
									shelter, where practical, at all levels up to the appropriate
									lifeboat and liferaft embarkation decks or the highest level
									served by the stairway, whichever level is the highest.  The
									width, number and continuity of the stairways should be
									satisfactory for the number of persons likely to use them.
 
 
- Access from the stairway enclosures to the lifeboat and liferaft
									embarkation areas should avoid high fire risk areas.
 
 
- Stairways serving only a space and a balcony in that space
									should not be considered as forming one of the required means of
										escape.
 
 
- If a radio room or wheelhouse has no direct access to the open
									deck, two means of escape should be provided, one of which may
									be a window of sufficient size or another means.
 
 
- Stairways are not to exceed 3,5 m vertical rise without the
									provision of a landing. 
 
 
- In the case where direct access to the appropriate survival
									craft embarkation deck as required by .1 and .2 is not
									practical, a ready accessible escape which will provide
									continuous fire shelter from the level of its origin to the
									appropriate open deck with subsequent direct passage to the
									embarkation deck can be accepted provided that these escape
									routes including external staircases, have emergency lighting
									and slip free surfaces under foot.
 
 
- Protection of access from the stairway enclosures to the
									lifeboat and liferaft embarkation areas should be provided
									either directly or through protected internal routes which have
									fire integrity and insulation values for stairway enclosures as
									determined by tables 1 and 2, as appropriate.
 
 
- Where public spaces span three or more open decks and contain
									combustibles such as furniture and give access to other enclosed
									spaces, each level within the space is to have two means of
									escape, one of which is to give access to a readily accessible
									escape which will provide continuous fire shelter from the level
									of its origin to the appropriate survival craft embarkation
									deck.
                14B.2.12.2 Two means of escape should be provided
								from each machinery space. In particular, the following provisions
								should be complied with: 
              
                - The two means of escape should consist of either: 
 (a) two sets of steel ladders as widely
									separated as possible, leading to doors in the upper part of the
									space similarly separated and from which access is provided to
									the appropriate survival craft embarkation decks. One of these
									ladders should provide continuous fire shelter from the lower
									part of the space to a safe position outside the space. This
									shelter is to be of steel or equivalent material, insulated
									where necessary, and provided with a self closing door at the
									lower end. If access is provided at other levels each level is
									to be provided with a steel or equivalent material self-closing
									door; or
 
 
 (b) one steel ladder leading to a door in the upper part of
									the space from which access is provided to the embarkation deck
									and additionally, in the lower part of the space and in a
									position well separated from the ladder referred to, a steel
									door capable of being operated from each side and which provides
									access to a safe escape route from the lower part of the space
									to the embarkation deck.
 
 
- One of the means of escape from any such space required by
									14B.2.12.2.1 may be dispensed with on sailing vessels with small
									machinery spaces, so long as either a door or a steel ladder and
									walkways provide a safe escape route to the embarkation deck
									with due regard being paid to the nature and location of the
									space and whether persons are normally employed in that
										space.
 
 
- Two means of escape should be provided from a machinery control
									room located within a machinery space, at least one of which
									should provide continuous fire shelter to a safe position
									outside the machinery space.
                14B.2.12.3 Lifts should not be considered as forming
								one of the required means of escape. 
              
                14B.2.12.4 In exceptional circumstances a single
								means of escape may be accepted for spaces other than accommodation
								spaces that are entered only occasionally, if the escape route does
								not pass through a galley, machinery space or watertight door. 
              
                14B.2.12.5 Adequate deck area is to be provided at
								assembly stations and embarkation areas having due regard to the
								expected number of persons.  Generally, assembly stations should be
								provided close to the embarkation stations. Each assembly station
								should have sufficient clear deck space to accommodate all persons
								assigned to assemble at that station, but at least 0.35 m2 per
								person. 
                
              
                14B.2.12.6 Emergency Escape Breathing Devices
               
               Emergency escape breathing devices (EEBD’s) should comply with the
								Fire Safety Systems Code. At least one spare emergency escape
								breathing device should be kept onboard. 
              
                14B.2.12.6.1 All vessels should carry at least two
								EEBD’s within accommodation spaces, and at least two EEBD’s should
								be carried in each main vertical zone. 
              
                14B.2.12.6.2 On all vessels, within the machinery
								spaces, EEBD’s should be situated ready for use at easily visible
								locations, which can be reached quickly and easily at any time in
								the event of fire. The number and location  should take into account
								the layout of the machinery space and the number of persons normally
								working in the space. The number and location of these devices
								should be indicated in the fire control plan. 
                
              
                14B.2.13 Ventilation systems
               
              
                14B.2.13.1 Ventilation ducts should be of
								non-combustible material.  Short ducts, however, not generally
								exceeding 2m in length and with a cross-section not exceeding 0.02m²
								need not be non-combustible, subject to the following
								conditions: 
              
                - they should be of a suitable material having regard to the risk
									of fire; 
- they should be used only at the end of the ventilation device;
									and 
- they should not be situated less than 600mm, measured along the
									duct, from an opening in an "A" or "B" class division including
									continuous "B" class ceilings.
                14B.2.13.2 Where ventilation ducts with a free
								cross-sectional area exceeding 0.02m² pass through class "A"
								bulkheads or decks, the opening should be lined with a steel sheet
								sleeve unless the ducts passing through the bulkheads or decks are
								of steel in the vicinity of passage through the deck or bulkhead and
								the ducts and sleeves should comply in this part with the
								following: 
              
                - Sleeves should have a thickness of at least 3mm and a length of
									at least 900mm. When passing through bulkheads, this length
									should be divided preferably into 450mm on each side of the
									bulkhead.  The ducts, or sleeves lining such ducts, should be
									provided with fire insulation. The insulation should have at
									least the same fire integrity as the bulkhead or deck through
									which the duct passes.
 
 
- Ducts with a free cross-sectional area exceeding 0.075m² should
									be fitted with fire dampers in addition to the requirements of
									.1 above. The fire damper should operate automatically but
									should also be capable of being closed manually from both sides
									of the bulkhead or deck. The damper should be provided with an
									indicator which shows whether the damper is open or closed. 
									Fire dampers are not required, however, where ducts pass through
									spaces surrounded by "A" class divisions, without serving those
									spaces, provided those ducts have the same fire integrity as the
									divisions which they pierce.
                14B.2.13.3 Ducts provided for the ventilation of a
								machinery space of category A, machinery spaces, galley, spaces
								containing vehicles or craft with fuel in their tanks or lockers
								storing such fuel, should not pass through accommodation spaces,
								service spaces or control stations unless they comply with the
								conditions specified in .1 to .4 or .5 and .6 below: 
              
                - they are constructed of steel having a thickness of at least 3mm
									and 5mm for duct widths or diameters of up to and including
									300mm and 760mm and over respectively and, in the case of ducts
									with widths or diameters between 300mm and 760mm, thickness
									should be obtained by interpolation;
 
 
- they are suitably supported and stiffened;
 
 
- they are fitted with automatic fire dampers close to the
									boundaries penetrated; and
 
 
- they are insulated to "A-60" standard from a machinery space or
									galley to a point at least 5m beyond each fire damper;
 
 or
 
 
- they are constructed of steel in accordance with .1 and .2
									above; and
 
 
- they are insulated to "A-60" standard throughout accommodation
									spaces, service spaces or control stations; except that
									penetrations of main zone divisions should also comply with the
									requirements of 14B.2.13.8.
                14B.2.13.4 Ducts provided for ventilation to
								accommodation spaces, service spaces or control stations should not
								pass through a machinery space of category A machinery spaces,
								galley, spaces containing vehicles or craft with fuel in their tanks
								or lockers storing such fuel, unless they comply with the conditions
								specified in .1 to .3 or .4 and .5 below:  
              
                - where they pass through a machinery space of category A or
									galley, ducts are constructed of steel in accordance with
									14B.2.13.3.1 & .2;
 
 
- automatic fire dampers are fitted close to the boundaries
									penetrated; and
 
 
- the integrity of the machinery space or galley boundaries is
									maintained at penetrations;
 
 
 or
 
 
- where they pass through a machinery space of category A or
									galley, ducts are constructed of steel in accordance with
									14B.2.13.3.1 & .2; and
 
 
- within a machinery space or galley, ducts are insulated to
									"A-60" standard; except that penetrations of main zone divisions
									should also comply with the requirements of 14B.2.13.8.
                14B.2.13.5 Ventilation ducts with a free
								cross-sectional area exceeding 0.02m² passing through "B" class
								bulkheads should be lined with steel sheet sleeves of 900mm in
								length divided preferably into 450mm on each side of the bulkheads,
								unless the duct is of steel for this length. 
              
                14B.2.13.6 For a control station outside machinery
								spaces and other normally manned control stations, practical
								measures should be taken to ensure that ventilation, visibility and
								freedom from smoke are maintained so that, in the event of fire, the
								machinery and equipment contained in the control station may be
								supervised and continue to function effectively.  Alternative and
								separate means of air supply should be provided; air inlets of the
								two sources of supply should be so disposed that the risk of both
								inlets drawing in smoke simultaneously is minimized.  These
								requirements need not apply to control stations situated on, and
								opening on to, an open deck, or where local closing arrangements
								would be equally effective. 
              
                14B.2.13.7 Exhaust duct(s) from a galley range
								should be constructed of "A" class divisions where passing through
								accommodation spaces and/or spaces containing combustible
								materials.  In addition to the requirements of 14B.2.13.3 An exhaust
								duct should be fitted with: 
              
                - a grease trap readily removable for cleaning;
 
 
- a fire damper located in the lower end of the duct;
 
 
- arrangements for shutting off the exhaust fans, operable from
									within the galley; and
 
 
- fixed means for extinguishing a fire within the duct.
                14B.2.13.8 When it is necessary for a ventilation
								duct to pass through a main vertical zone division, a fail-safe
								automatic closing fire damper should be fitted adjacent to the
								division.  The damper should also be capable of being manually
								closed from each side of the division.  The operating position
								should be readily accessible and be marked in red light-reflecting
								colour.  The duct between the division and the damper should be of
								steel or other equivalent material and, if necessary, insulated to
								comply with the requirements of SOLAS regulation II-2/9.3.1.  The
								damper should be fitted on at least one side of the division with a
								visible indicator showing whether the damper is in the open
								position. 
              
                14B.2.13.9 Inlets and outlets of ventilation systems
								should be capable of being closed from outside the space being
								ventilated. 
              
                14B.2.13.10 Power ventilation of accommodation
								spaces, service spaces, control stations and machinery spaces should
								be capable of being stopped from an easily accessible position
								outside the space being served.  This position should not be readily
								cut off in the event of a fire in the spaces served.  The means
								provided for stopping the power ventilation of a machinery space
								should be entirely separate from the means provided for stopping
								ventilation of other spaces. 
              
                14B.2.13.11 Where public spaces span three or more
								open decks and contain combustibles such as furniture and other
								enclosed spaces, the space is to be equipped with a smoke extraction
								system. The smoke extraction system is to be activated by the smoke
								detection system required by 14B.2.14 and is to be capable of manual
								control. The fans are to be capable of exhausting the entire volume
								within the space in not more than 10 min. 
              
                14B.2.13.12 Store-rooms containing highly flammable
								products are to be provided with ventilation arrangements that are
								separate from other ventilation systems. Ventilation is to be
								arranged to prevent the build up of flammable vapours at high and
								low levels. The inlets and outlets of ventilators are to be
								positioned so that they do not draw from or vent into an area which
								would cause undue hazard, and are to be fitted with spark
								arresters. 
              
                14B.2.13.13 Ventilation systems serving Category 'A'
								machinery spaces are to be independent of systems serving other
								spaces. 
              
                14B.2.13.14 All enclosed spaces containing free
								standing fuel tanks are to be ventilated independently of systems
								serving other spaces. 
              
                14B.2.13.15 Ventilation is to be provided to prevent
								the accumulation of dangerous concentrations of flammable gas which
								may be emitted from batteries.  
              
                14B.2.13.16 Ventilation openings may be fitted in
								and under the lower parts of cabin and public space doors in
								corridor bulkheads. The total net area of any such openings is not
								to exceed 0,05 m2. 
              
                14B.2.13.17 For spaces containing vehicles or craft
								with fuel in their tanks or lockers storing such fuels, see 14B.1.
								For additional requirements for the ventilation of domestic gaseous
								fuel, see 14B.2.20. 
              
                14B.2.13.18 Ducts provided for exhaust ventilation
								from laundries are to be fitted with suitable located cleaning and
								inspection openings. 
              
                14B.2.13.19 All fire dampers should comply with IMO
								FTP Code, Annex 1, Part 3. 
                
              
                
                14B.2.14 Fixed fire detection and fire alarm systems and
									automatic sprinkler, fire detection and fire alarm
									systems
               
              
                 Purpose
               
              The purpose of this section is to detect a fire in the space of
								origin and to provide for alarm for safe escape and fire-fighting
								activity. For this purpose, the following functional requirements
								should be met: 
              
                - fixed fire detection and fire alarm system installations should
									be suitable for the nature of the space, fire growth potential
									and potential generation of smoke and gases; and
- manually operated call points should be placed effectively to
									ensure a readily accessible means of notification.
                14B.2.14.1 Each separate zone in all accommodation
								and service spaces, except spaces which afford no substantial fire
								risk such as void spaces, sanitary spaces, etc., should be provided
								throughout with an automatic sprinkler, fire detection and fire
								alarm system of an approved type and complying with the requirements
								of SOLAS, Part C. regulation II-2/7 and the IMO FSS Code, Chapter 8,
								or an equivalent standard acceptable to the administration. The
								system should be designed to enable simultaneous operation of all
								sprinklers fitted in the most hydraulically  demanding area. The
								minimum area for simultaneous operation may be taken as the largest
								area bounded by A0 class divisions or the breadth of the vessel
								squared, whichever is the greater. In addition, a fixed fire
								detection and fire alarm system of an approved type complying with
								the requirements of SOLAS II-2/7 and the IMO FSS Code, Chapter 9
								should be installed and arranged to provide smoke detection in
								corridors, stairways and escape routes within accommodation spaces;  
              
                
 
14B.2.15    Fire
									detection and alarms 
              
                14B.2.15.1 Manually operated call points complying
								with the requirements of SOLAS II-2/7 and the IMO FSS Code, Chapter
								9 should be installed. 
              14B.2.15.2 For vessels having a freeboard length of 85 m or more, a
								public address system complying with the requirements of SOLAS
								III/6.5 is to be available throughout the accommodation and service
								spaces and control stations and open decks. 
                
              
                
                14B.2.16 Oil fuel arrangements
               
              
                14B.2.16.1 Arrangements for the storage,
								distribution and utilisation of oil fuel are to be such as to
								minimise the risk of fire or explosion. 
              
                14B.2.16.2 As far as practicable, oil fuel tanks are
								to be part of the vessel's structure and are to be located outside
								Category 'A' machinery spaces. 
              
                14B.2.16.3 Where oil fuel tanks, other than double
								bottom tanks, are necessarily located adjacent to or within Category
								'A' machinery spaces, at least one of their vertical sides is to be
								contiguous to the machinery space boundaries, and is preferably to
								have a common boundary with the double bottom tanks, and the area of
								the tank boundary common with the machinery spaces is to be kept to
								a minimum. Where the vertical boundary of a tank directly exposed to
								a machinery space meets the vessel's side plating at an acute angle,
								a small horizontal surface at the base of the tank, necessary to
								accommodate practical constructional considerations may be
								permitted. If the arrangement of the machinery is such that a tank
								with a large horizontal surface at the base is necessary then a
								cofferdam with suitable ventilation arrangements, to protect the
								base of the tank from the effect of a machinery space fire, will be
								specially considered. Oil fuel tanks situated within the boundaries
								of Category 'A' machinery spaces are not to contain oil fuel having
								a flashpoint of less than 60°C. Except for vessels constructed of
								materials other than steel, where steel tanks should be provided,
								the use of free standing oil fuel tanks is prohibited. 
                
              
                
                14B.2.17 Lubricating oil arrangements
               
              Arrangements for the storage, distribution and utilisation of oil
								used in pressure lubrication systems are to be such as to minimise
								the risk of fire or explosion. 
                
              
                14B.2.18 Arrangements for other flammable oils 
               Arrangements for the storage, distribution and utilisation of other
								flammable oils employed under pressure in power transmission
								systems, control and activating systems and heating systems are to
								be such as to minimise the risk of fire or explosion. 
                
              
                
                14B.2.19 Prohibition of carriage of flammable oils in
									forepeak tanks
               
               Oil fuel, lubricating oil and other flammable oils are not to be
								carried in forepeak tanks. 
                
              
                
                14B.2.20 Arrangements for gaseous fuel for domestic
									purposes
               
               Where gaseous fuel is used for domestic purposes, the arrangements
								for the storage, distribution and utilization of the fuel are to be
								such that, having regard to the hazards of fire and explosion which
								the use of such fuel may entail, the safety of the vessel and the
								persons on board is preserved. The installation is to be in
								accordance with recognised National or International Standards and
								is to meet the requirements contained in 14A.5. 
                
              
                14B.2.21 Space heaters
               
               Space heaters, if used, are to be fixed in position and so
								constructed as to reduce fire risks to a minimum. The design and
								location of these units is to be such that clothing, curtains or
								other similar materials cannot be scorched or set on fire by heat
								from the unit.