MSC.1/Circ.1314

Application of  SOLAS Regulation II-2/10 and chapter 12 of the FSS Code related to emergency fire pump capacity

  1. The Committee, at its eighty-sixth session (27 May to 5 June 2009), having considered the proposal by the Sub-Committee on Fire Protection, at its fifty-third session, with regard to the
    application of SOLAS regulation II-2/10 and chapter 12 of the FSS Code related to emergency fire pump capacity, agreed to the following interpretation:


    “Interpretation of chapter 12 of the FSS Code
    The emergency fire pump shall as a minimum comply with paragraph 2.2.1.1. Where
    a fixed water-based fire-extinguishing system installed for the protection of the
    machinery space in accordance with SOLAS regulation II-2/10.4.1.1 is supplied by the
    emergency fire pump, then the emergency fire pump capacity should be adequate to
    supply the fixed fire-extinguishing system at the required pressure plus two jets of water.
    The capacity of the two jets should in any case be calculated at not less than 25 m3/h.

    The minimum pressure referred to in paragraph 2.2.1.2 should be understood to
    mean 0.27 N/mm2.”

  2. Member Governments are invited to use the above interpretations when applying SOLAS regulation II-2/10 and chapter 12 of the FSS Code related to emergency fire pump capacity, and bring them to the attention of ship designers, shipowners, equipment manufacturers, test