Warning For safety, all tests should be carried out in a suitably constructed
fume enclosure (see 4.2).
8.1 Preparation
8.1.1 Ensure that the means of extinguishment are close at hand (see 4.3).
8.1.2 Open out the test rig and thread the covering fabric
and, if any, the fabric interliner behind the hinge bar.
8.1.3 Place the filling pieces under the covering fabric and, if any, the
fabric interliner locating the filling pieces in the frame recesses, and allowing
approximately 20 mm of fabric to wrap round the inside of the frames.
8.1.4 Lock the frames at right angles using the bolts or pins ensuring that
the filling components are not displaced.
8.1.5 Fasten the
fabric over the top, bottom and sides of the frame using clips and ensure that the
fabric or fabrics are secured and under even tension.
8.2 Smouldering cigarette test
8.2.1
Light a cigarette (see 5.2) and draw air through it until the tip glows brightly. Not
more than 8 mm of the cigarette shall be consumed in this operation.
8.2.2 Place the smouldering cigarette in position along the junction
between the vertical and horizontal test pieces, allowing at least 50 ‡ofrom the
nearest side edge, or from any marks left by any previous test, to the cigarette and
simultaneously start the clock.
8.2.3 Observe the progress of
combustion, and record any evidence of progressive smouldering (see clause 2) or
flaming in the interior and/or cover.
Note: The detection of smouldering may
be difficult and is made easier if a watch is kept for smoke emerging at points at a
distance from the cigarette. Smoke is most easily viewed by looking down a rising
column by means of a mirror. 8.2.4 If progressive smouldering or flaming
of the upholstery components is observed at any time within a period of one hour of
the placement of the cigarette, extinguish the test piece and record a fail result for
the smouldering cigarette test.
8.2.5 If progressive
smouldering or flaming is not observed within the one hour period, or if the cigarette
fails to smoulder its complete length, repeat the test with a new cigarette placed in
a fresh position not less than 50 ‡ofrom any previous test damage. If progressive
smouldering or flaming is not observed in this retest, or if the cigarette fails to
smoulder its complete length, record a pass result for the smouldering cigarette test
unless the test piece fails the final examination specified in 8.4. Otherwise,
extinguish the test piece and record a fail result.
Note: This repeat test may
be run concurrently with the first test. 8.3 Butane flame test
8.3.1 Light
the butane emerging from the burner tube, adjust the gas flow to the appropriate rate
(see 5.3) and allow the flame to stabilize for at least 2 min.
8.3.2 Position the burner tube axially along the junction between the seat
and back so that the flame is not less than 50 mm from the nearest side edge, or from
any marks left by any previous test, and simultaneously start the clock.
8.3.3 Allow the gas to burn for a period of 20±1 s, then
terminate by carefully removing the burner tube from the test pieces.
8.3.4 Observe for flaming or progressive smouldering (see clause 2) in the
interior and/or cover. Disregard flames, afterglow, smoking or smouldering that cease
within 120 s of the removal of the burner tube.
8.3.5 If
flaming or progressive smouldering of the upholstery components is observed,
extinguish the test piece. Record a fail result for the butane flame ignition source
test.
8.3.6 If flaming or progressive smouldering is not
observed, repeat the test at a fresh position, as described in 8.3.2. If flaming or
progressive smouldering is not observed in this retest, record a pass result for the
butane flame ignition source test unless the test piece fails the final examination
specified in 8.4. Otherwise extinguish the test piece and record a fail result.
8.4 Final examination
Cases
of progressive smouldering undetected from the outside have been reported. Immediately
after completion of the test programme on the assembly, dismantle and examine it
internally for progressive smouldering. If this is present, extinguish the test piece
and record a fail result for the relevant test source. For safety reasons, ensure that
all smouldering has ceased before the rig is left unattended.