Onderwerp: Bezoek-historie

FTP-Code - 1998 International Code for Application of Fire Test Procedures
Geldigheid:01-07-2006 t/m Versie:vergelijk Status: Geldig vandaag

Dit onderwerp bevat de volgende rubrieken.

Ingangsdatum: 01-07-1998

1 Scope

Ingangsdatum: 01-07-1998

1.1 This Code is intended for use by the Administration and the competent authority of the flag State when approving products for installation in ships flying the flag of the flag State in accordance with the fire safety requirements of the International Convention for the Safety of Life at Sea, 1974, as amended.

1.2 This Code shall be used by the testing laboratories when testing and evaluating products under this Code.

2 Application

Ingangsdatum: 01-07-1998

2.1 This Code is applicable for the products which are required to be tested, evaluated and approved in accordance with the Fire Test Procedures Code as referenced in the Convention.

2.2 Where reference to the Code is indicated in the Convention by the terminology "... in accordance with the Fire Test Procedures Code" the subject product shall be tested in accordance with the applicable Fire Test Procedures or procedures as referred to in paragraph 4.1.

2.3 Where reference is only made to a product's fire performance in the Convention using such terminology as "... and their exposed surfaces shall have low flame spread characteristics", the subject product shall be tested in accordance with the applicable Fire Test Procedures or procedures as referred to in paragraph 4.1.

3 Definitions

Ingangsdatum: 01-07-1998


3.1"Fire Test Procedures Code" means the International Code for Application of Fire Test Procedures as defined in Chapter II-2 of the Convention, as amended.

3.2 "Test expiry date" means the last date on which the given test procedure may be used to test and subsequently approve any product under the Convention.

3.3 "Approval expiry date" means the last date on which the subsequent approval is valid as proof of meeting the fire safely requirements of the Convention.

3.4 "Administration" means the Government of the State whose flag the ship is entitled to fly.

3.5 "Competent authority" means an organization authorized by the Administration to perform functions required by this Code.

3.6 "Laboratory recognized by the Administration" means a testing laboratory which is acceptable to the Administration concerned. Other testing laboratories may be recognized on a case-by-case basis for specific approvals as agreed upon by the Administration concerned.

3.7 "Convention" means the International Convention for the Safety of Life at Sea, 1974, as amended.

3.8 "Standard fire test" means a test in which specimens are exposed in a test furnace to temperatures corresponding approximately to the standard time-temperature curve.

3.9 "Standard time-temperature curve" means the time-temperature curve defined by the formula:

T = 345 log10(8t + 1) + 20

where:

T is the average furnace temperature (0°C)

t is the time (minutes).

4 Testing

Ingangsdatum: 01-07-1998

4.1 Fire Test Procedures

4.1.1 Annex 1 of this Code presents the required test procedures which shall be used in testing products as a basis for approval (including renewal of approval), except as provided in section 8.

4.1.2 The test procedures identify the test methods and the acceptance and classification criteria.

4.2 Testing laboratories

4.2.1 The tests shall be carried out in testing laboratories recognized by the Administrations concerned.

4.2.2 When recognizing a laboratory, the Administration shall consider the following criteria:
.1 that the laboratory is engaged, as a regular part of its business, in performing inspections and tests that are the same as, or similar to, the tests as described in the applicable part;
.2 that the laboratory has access to the apparatus, facilities, personnel and calibrated instruments necessary to perform these tests and inspections; and
.3 that the laboratory is not owned or controlled by a manufacturer, vendor or supplier of the product being tested.

4.2.3 The testing laboratory shall use a quality control system audited by the competent authority.

4.3 Test reports

4.3.1 The test procedures state the required contents of the test reports.

4.3.2 In general, a test report is the property of the sponsor of the test.

5 Approval

Ingangsdatum: 01-07-1998

5.1 General

5.1.1 The Administration shall approve products in accordance with their established approval procedures by using the type approval procedure (see paragraph 5.2) or the case-by-case approval (see paragraph 5.3).

5.1.2 The Administration may authorize competent authorities to issue approvals on their behalf.

5.1.3 An applicant who seeks approval shall have the legal right to use the test reports on which the application is based (see paragraph 4.3.2).

5.1.4 The Administration may require that the approved products are provided with special approval markings.

5.1.5 The approval shall be valid when the product is installed on board a ship. If a product is approved when manufactured, but the approval expires before the product is installed on the ship, the product may be installed as approved material, provided that the criteria have not changed since the expiry date of the approval certificate.

5.1.6 The application for approval shall be sought from the Administration or competent authority. The application shall contain at least the following:
.1 the name and address of the applicant and of the manufacturer;
.2 the name or trade name of the product;
.3 the specific qualities for which approval is sought;
.4 drawings or descriptions of the assembly and materials of the product as well as instructions, where applicable, for its installation and use; and
.5 a report on the fire test(s).

5.1.7 Any significant alteration to a product shall make the relevant approval to cease to be valid. To obtain a new approval, the product shall be retested.

5.2 Type approval

5.2.1 The type approval certificates shall be issued and renewed on basis of the test reports of the applicable fire tests (see section 4).

5.2.2 The Administration shall require that the manufacturers have a quality control system audited by a competent authority to ensure continuous compliance with the type approval conditions. Alternatively, the Administration may use final product verification procedures where the compliance with the type approval certificate is verified by a competent authority before the product is installed on board ships.

5.2.3 The type approval certificates shall be valid no more than 5 years from the date of issue.

5.2.4 Type approval certificates shall include at least the following:
.1 identification (name or trade name and description) of the product;
.2 classification and any restrictions in the use of the product;
.3 name and address of the manufacturer and applicant;
.4 test method(s) used in test(s);
.5 identification of the test report(s) and applicable statements (including date of issue, possible file number and the name and address of the testing laboratory);
.6 date of issue and possible number of the type approval certificate;
.7 expiration date of the certificate; and
.8 name of the issuing body (competent authority) and, if applicable, authorization.

5.2.5 In general, the type approved products may be installed for their intended use on board ships flying the flag of the approving Administration.

5.3 Case-by-case approval

5.3.1 The case-by-case approval means approval where a product is approved for installation on board a specific ship without using a type approval certificate.

5.3.2 The Administration may approve products using the applicable test procedures for specific ship applications without issuing a type approval certificate. The case-by-case approval is only valid for the specific ship.

6 Products which may be installed without testing and/or approval

Ingangsdatum: 01-07-1998

Annex 2 of this Code specifies the groups of products, which (if any) are considered to comply with the specific fire safety regulations of the Convention and which may be installed without testing and/or approval.

7 Use of equivalents and modern technology

Ingangsdatum: 01-07-1998

7.1 To allow modem technology and development of products, the Administration may approve products to be installed on board ships based on tests and verifications not specifically mentioned in this Code but considered by the Administration to be equivalent with the applicable fire safety requirements of the Convention.

7.2 The Administration shall inform the Organization of approvals referenced to in paragraph 7.1 in accordance with Regulation I/5 of the Convention and follow the documentation procedures as outlined below:
.1 in the case of new and unconventional products, a written analysis as to why the existing test method(s) cannot be used to test this specific product;
.2 a written analysis showing how the proposed alternative test procedure will prove performance as required by the Convention; and
.3 a written analysis comparing the proposed alternative test procedure to the required procedure in the Code.

8 Period of grace for other test procedures

Ingangsdatum: 01-07-1998

8.1 The newest test procedures adopted by the Organization are considered being the most suitable for demonstrating that the products concerned comply with the applicable fire safety requirements of the Convention.

8.2 Notwithstanding what is said elsewhere in this Code, the Administration may use established test procedures and acceptance criteria, other than those in Annex 1 to this Code, when approving products to comply with the fire safety requirements of the Convention to allow a practicable period of grace for the testing laboratories to obtain testing equipment, for the industry to re-test their products and for the Administrations to provide the necessary new certification. For such other test procedures and acceptance criteria the test expiry dates and the approval expiry dates are given in Annex 3 to this Code.

9 List of references

The following IMO Assembly Resolutions and ISO standards are referred to in parts 1 to 9 of Annex 1 to the Code:

.1 Resolution A.471(XII) - "Recommendation on test method for determining the resistance to flame of vertically supported textiles and films";

.2 Resolution A.563(14) - "Amendments to the Recommendation on test method for determining the resistance to flame of vertically supported textiles and films (Resolution A.471(XII))";

.3 Resolution A.652(16) - "Recommendation on Fire Test Procedures for upholstered furniture";

.4 Resolution A.653(16) - "Recommendation on improved Fire Test Procedures for surface flammability of bulkhead, ceiling and deck finish materials";

.5 Resolution A.687(17) -"Fire Test Procedures for ignitability of primary deck coverings";

.6 Resolution A.688(17) - " Fire Test Procedures for ignitability of bedding components";

.7 Resolution A.753(18) - "Guidelines for the application of plastic pipes on ships";

.8 Resolution A.754(18) - "Recommendation on fire resistance tests for "A", "B" and "F" class divisions";

.9 ISO 1182:1990 - "Fire test - Building materials - Non-combustibility test";

.10 ISO 1716:1973 - "Building materials - Determination of calorific potential";

Ingangsdatum: 01-07-2002

The following IMO Assembly Resolutions and ISO standards are referred to in parts 1 to 9 of Annex 1 to the Code:

.1 Resolution A.471(XII) - "Recommendation on test method for determining the resistance to flame of vertically supported textiles and films";

.2 Resolution A.563(14) - "Amendments to the Recommendation on test method for determining the resistance to flame of vertically supported textiles and films (Resolution A.471(XII))";

.3 Resolution A.652(16) - "Recommendation on Fire Test Procedures for upholstered furniture";

.4 Resolution A.653(16) - "Recommendation on improved Fire Test Procedures for surface flammability of bulkhead, ceiling and deck finish materials";

.5 Resolution A.687(17) " Fire Test Procedures for ignitability of primary deck coverings";

.6 Resolution A.688(17) - " Fire Test Procedures for ignitability of bedding components";

.7 Resolution A.753(18) - "Guidelines for the application of plastic pipes on ships";

.8 Resolution A.754(18) - "Recommendation on fire resistance tests for "A", "B" and "F" class divisions";

.9 ISO 1182:1990 - "Fire test - Building materials - Non-combustibility test";

.10 ISO 1716:1973 - "Building materials - Determination of calorific potential"; and

.11 ISO 5659:1994 - "Plastics - Smoke generation, Part 2 Determination of optical density by a single chamber test".

.12 resolution MSC.40(64), as amended by resolution MSC.90(71) , Standard for qualifying marine materials for high-speed craft as fire-restricting materials; and

.13 resolution MSC.45(65) , Test procedures for fire-resisting divisions of high-speed craft".

ANNEX 1 Fire Test Procedures Preamble

Ingangsdatum: 01-07-1998

PART 01 Non-combustibility test

Ingangsdatum: 01-07-1998

1 Application

Ingangsdatum: 01-07-1998

1.1 Where a material is required to be non-combustible, it shall be determined in accordance with this part.

1.2 If a material passes the test as specified in section 2, it shall be considered as "non-combustible" even if it consists of a mixture of inorganic and organic substances.

2 Fire Test Procedures

Ingangsdatum: 01-07-1998

2.1 The non-combustibility shall be verified in accordance with the test procedure in the standard ISO 1182:1990 except that instead of Annex A "Criteria for evaluation" of this standard all the following criteria shall be satisfied:
.1 the average furnace thermocouple temperature rise as calculated in 8.1.2 of ISO 1182 does not exceed 30°C;
.2 the average surface thermocouple temperature rise as calculated in 8.1.2 of ISO 1182 does not exceed 30°C;
.3 the mean duration of sustained flaming as calculated in 8.2.2 of ISO 1182 does not exceed 10 s; and
.4 the average mass loss as calculated in 8.3 of ISO 1182 does not exceed 50%.

2.2 The test report shall include the following information:
.1 name of testing body;
.2 name of manufacturer of the material;
.3 date of supply of the materials and of tests;
.4 name or identification of the material;
.5 description of the material;
.6 density of the material;
.7 description of the specimens;
.8 test method;
.9 test results including all observations;
.10 designation of the material according to the test criteria specified in paragraph 2.1 above.

PART 02 Smoke and toxicity test

Ingangsdatum: 01-07-1998

1 Application

Ingangsdatum: 01-07-1998

Where a material is required not to be capable of producing excessive quantities of smoke and toxic products or not to give rise to toxic hazards at elevated temperatures, the material shall comply with this part.

2 Fire Test Procedures

Ingangsdatum: 01-07-1998
2.1 General
Ingangsdatum: 01-07-1998

Smoke generation tests shall be conducted in accordance with standard ISO 5659:1994, Part 2 and additional test procedures as described in this part of the Code. To carry out the tests in accordance with this standard, modifications of the arrangements and procedures to the ISO standard shall be made, if necessary.
2.2 Test specimen
Ingangsdatum: 01-07-1998

Preparation of test specimen shall be in accordance with the practice outlined in Resolutions A.653(16), A.687(17) and A.753(18). In the case of cables, only specimens of those with maximum insulation thickness need be tested.
2.3 Test conditions
Ingangsdatum: 01-07-1998

Irradiance to the specimen during the test shall be kept constant. Three specimens shall be tested under each of the following conditions:
.1 irradiance of 25 kW/㎡ in the presence of pilot flame;
.2 irradiance of 25 kW/㎡ in the absence of pilot flame; and
.3 irradiance of 50 kW/㎡ in the absence of pilot flame.
2.4 Duration of tests
Ingangsdatum: 01-07-1998

The test shall be carried out for at least 10 min. If the minimum light transmittance value has not been reached during the 10-minute exposure, the test shall be continued for a further 10-minute period.
2.5 Test results
Ingangsdatum: 01-07-1998

2.5.1 Specific optical density of smoke (Ds) as defined below shall be recorded during the test period at least every 5 s:

Ds = (V/(A*L))*log10(Io/l)

where:

V = total volume of the chamber (m3)

A = exposed area of the specimen (m2)

L = optical length (m) of smoke measurement

Io = light intensity before the test

I = light intensity during the test (after absorbtion by the smoke).

2.5.2 When making toxicity measurements, the sampling of fumes shall be made during the testing of the second or the third specimen at each test condition, from the geometrical centre of the chamber within 3 min of the time when the maximum specific optical density of smoke is reached. The concentration of each toxic gas shall be determined as ppm in the chamber volume.
2.6 Classification criteria


2.6.1 Smoke

An average (Dm) of the maximum of Ds of three tests at each test condition shall be calculated.

.1 for materials used as surface of bulkheads, linings or ceilings, the Dm shall not exceed 200 in any test condition;

.2 for materials used as primary deck covering, the Dm shall not exceed 400 in any test condition;

.3 for materials used as floor covering, the Dm shall not exceed 500 in any test condition; and

.4 for plastic pipes and electric cables, the Dm shall not exceed 400 in any test condition.

2.6.2 Toxicity

The gas concentration measured at each test condition shall not exceed the following limits:

CO                   1450 ppm

HCl                  600 ppm

HF                    600 ppm

NOx                                    350 ppm

HBr                  600 ppm

HCN                 140 ppm

SO2                                    120 ppm

Ingangsdatum: 01-07-1998
Geldig tot en met: 30-06-2006


2.6.1 Smoke

An average (Dm) of the maximum of Ds of three tests at each test condition shall be calculated.

.1 for materials used as surface of bulkheads, linings or ceilings, the Dm shall not exceed 200 in any test condition;

.2 for materials used as primary deck covering, the Dm shall not exceed 400 in any test condition;

.3 for materials used as floor covering, the Dm shall not exceed 500 in any test condition; and

.4 for plastic pipes and electric cables, the Dm shall not exceed 400 in any test condition.

2.6.2 Toxicity

The gas concentration measured at each test condition shall not exceed the following limits:

CO                   1450 ppm

HCl                  600 ppm

HF                    600 ppm

NOx                                    350 ppm

HBr                  600 ppm

HCN                 140 ppm

SO2                                    120 ppm

2.6 Classification criteria
Ingangsdatum: 01-07-2006


2.6.1 Smoke

An average (Dm) of the maximum of Ds of three tests at each test condition shall be calculated.

.1 for materials used as surface of bulkheads, linings or ceilings, the Dm shall not exceed 200 in any test condition;

.2 for materials used as primary deck covering, the Dm shall not exceed 400 in any test condition;

.3 for materials used as floor covering, the Dm shall not exceed 500 in any test condition; and

.4 for plastic pipes and electric cables, the Dm shall not exceed 400 in any test condition.

2.6.2 Toxicity

The gas concentration measured at each test condition shall not exceed the following limits:

CO                 1450 ppm

 

HCl                 600 ppm

HF                  600 ppm

NOx                      350 ppm

HBr                 600 ppm

HCN                140 ppm

SO2                      120 ppm (200 ppm for floor coverings)

2.7 Test report
Ingangsdatum: 01-07-1998

A test report shall contain the following information:

.1 type of the material, i.e. surface finish, floor covering, primary deck covering, pipes, etc;

.2 trade name of the material;

.3 description of the material;

.4 construction of the specimen;

.5 name and address of the manufacturer of the material;

.6 Dm at each heating and ignition condition;

.7 concentrations of toxic gases in ppm, if applicable;

.8 judgement according to paragraph 2.6;

.9 name and address of the testing laboratory; and

.10 date of testing

3 Additional requirements

Ingangsdatum: 01-07-1998

3.1 Part 5 of this Annex is also applicable to paints, floor coverings, varnishes and other finishes used on exposed interior surfaces.

3.2 Part 6 of this Annex is also applicable to the primary deck coverings.

PART 03 Test for "A", "B" and "F" class divisions

Ingangsdatum: 01-07-1998

1 Application

Ingangsdatum: 01-07-1998

Where products (such as decks, bulkheads, doors, ceilings, linings, windows, fire dampers, pipe penetrations and cable transits) are required to be "A" or "B" or "F" class divisions, they shall comply with this part.

2 Fire Test Procedures

Ingangsdatum: 01-07-1998

2.1 The products shall be tested and evaluated in accordance with the Fire Test Procedures specified in Resolution A.754(18). This contains test procedures also for windows, fire dampers and pipe and duct penetrations in its appendices.

2.2 Specimen sizes

2.2.1 For the purpose of this Code, the first sentence of paragraphs 2.1.1, 2.4.1 and 2.7.1 of the Annex to Resolution A.754(18) is replaced by the following:

"The minimum overall dimensions of test specimen, including the perimeter details at the top, bottom and vertical edges, are 2,440 mm width and 2,500 mm height, except that the minimum overall dimensions of 2,440 mm in height and 4.65 m2 in the exposed surface of the test specimen may be used in testing up to 31 December 1998. The approval expiry date is 31 December 2003 for approvals based on tests with such smaller test specimen."

2.2.2 For the purpose of this Code, the first sentence of paragraphs 2.2.1, 2.5.1 and 2.8.1 of the Annex to Resolution A.754(18) is replaced by the following: "The minimum overall dimensions of test specimen, including the perimeter details at all the edges, are 2,440 mm width and 3,040 mm length, except that the minimum overall dimensions of 2,440 mm in length and 4.65 m2 in the exposed surface of the test specimen may be used in testing up to 31 December 1998. The approval expiry date is 31 December 2003 for approvals based on tests with such smaller test specimen."

2.2.3 The specimen sizes shall he given in the test reports

2.3 Where thermal radiation through windows is required to be limited, the window assembly may be tested and evaluated in accordance with Appendix 1 of this part.

2.4 Where ceilings or linings are required to be continuous "B" class ceilings or linings they may be tested and evaluated in accordance with Appendix 2 of this part.

3 Additional requirements

Ingangsdatum: 01-07-1998

3.1 The integrity of class "B" constructions shall be achieved with non-combustible materials. Adhesives used in the construction of the specimen are not required to be non-combustible; however, for the purpose of this Code, they shall have low flame-spread characteristics.

3.2 Materials placed at "B" class panel joints for avoiding vibration or noise transmission shall be of low flame spread characteristics and fire tested with "B" class divisions along which they are used. However, such materials shall be non-combustible if they are necessary to support the non-combustible "B" class structure or to achieve the required integrity.

3.3 Doors and shutters, which are fitted above the bulkhead deck and which are required to meet both fire protection and watertight requirements, shall comply with the fire protection requirements as required in the Convention, for the divisions where they are installed. The watertight doors fitted below the bulkhead deck are not required to be insulated.

4 Other references

Ingangsdatum: 01-07-1998

4.1 The non-combustibility of materials used in "A" and "B" class divisions shall be verified in accordance with part 1.

4.2 Where combustible veneers are allowed to be provided in "A" and "B" class divisions, the low flame spread characteristics of such veneers, if required, shall be verified in accordance with part 5.

APPENDIX 1 Thermal radiation test supplement to fire resistance tests for windows in "A", "B" and "F" class divisions

Ingangsdatum: 01-07-1998
1 Scope
Ingangsdatum: 01-07-1998

1.1 This Appendix specifies a procedure for measuring heal flux through windows as a basis for characterizing their ability to limit the heat radiation in order to prevent the spread of fire and to enable escape routes to pass near the windows.

1.2 This procedure is an optional requirement and may be requested by some Administrations for windows in specific areas of a ship.
2 Test procedure
Ingangsdatum: 01-07-1998

2.1 The window should be tested in accordance with Resolution A.754(18) using the additional instrumentation as described below.

2.2 The term "window" includes windows, side scuttles and any other glazed opening provided for light transmission or vision purposes in a fire resistant division. The term "fire resistant division" includes bulkheads and doors.
3 Additional instrumentation
Ingangsdatum: 01-07-1998

3.1 Additional instrumentation consists of a restricted-view total-heat fluxmeter calibrated with the restricted view to indicate incident heat flux. The fluxmeter should be water-cooled and capable of measuring heat flux 0 to 60 kW/m2. The fluxmeter should be calibrated at least once a year against a standard device.

3.2 The fluxmeter should be placed perpendicular to the centre of the window being tested, and in a position such that the centre of the fluxmeter's view coincides with the centre of the window (see the figure). The fluxmeter should be located at a distance greater than 0.5 m from the window, such that the view of the fluxmeter just includes part of the frame. However, the fluxmeter should not be located more than 2.5 m from the window. The dimension of the boundary and window frame seen by the fluxmeter, which remains outside the window should not exceed 10% of the total width seen by the fluxmeter on the surface of the sample. It should be calculated on the basis of restricted view angle of the fluxmeter and its distance to the sample surface.

3.3 For windows whose greater dimension is less than 1.57 times the smaller dimension, only one fluxmeter is needed.

3.4 For oblong windows whose greater dimension is more than 1.57 times the smaller dimension, additional fluxmeters should be provided. The distance of the fluxmeters from the window should be adjusted such that the fluxmeters' view covers at least 50% of the window. However, the fluxmeters should not be located less than 0.5 m nor more than 2.5 m from the window.
4 Classification criteria
Ingangsdatum: 01-07-1998
4.1 The peak heat flux (Ew) should be measured for the first 15 min of the test, for the first 30 min of the test, and for the entire duration of the test (i.e. 60 min for class "A" and 30 min for class "B" boundaries).

 

4.2 The peak heat fluxes (Ew) measured in accordance with paragraph 4.1 should be compared against the reference value (Ec) from the table.

 

4.3 If (Ew) is less than (Ec), the window is acceptable for installation in a boundary of the corresponding fire resistant classification.

 

Table 1 - Criteria for heat flux

Fire resistant division classification

Time period from beginning of test to

Heat flux Ec (kW/m2)

A-0

60 minutes

56.5

A-15

15 minutes
60 minutes

2.34
8.0

A-30

30 minutes
60 minutes

2.34
6.4

A-60

60 minutes

2.34

B-0

30 minutes

36.9

B-15

15 minutes
30 minutes

2.34
4.3

 

APPENDIX 2 Continuous "B" class divisions

Ingangsdatum: 01-07-1998
1 Scope
Ingangsdatum: 01-07-1998

1.1 This Appendix specifies the procedure for testing linings and ceilings for verifying that they are "continuous 'B' class linings" and "continuous 'B' class ceilings" and for evaluating full constructions to be "continuous 'B' class constructions".

1.2 This procedure is an optional requirement and may be requested by some Administrations for continuous "B" class divisions.
2 Test procedure and evaluation
Ingangsdatum: 01-07-1998

2.1 The linings, ceilings and constructions should be evaluated in accordance with Resolution A.754(18) using the arrangements described below.

2.2 The ceilings should be tested in accordance with paragraph 2.8 of the Annex to Resolution A.754(18) except that the ceiling should be mounted on the horizontal furnace so that at least 150 mm high "B" class bulkheads are mounted on the furnace and the ceiling is fixed to these partial bulkheads by using the joining method as is intended to be used in practice. Such ceilings and the joining methods should be evaluated as required for ceilings in accordance with Resolution A.754(18) and accordingly they should be classified as "continuous 'B' (B-0 or B- 15, as applicable) class ceilings".

2.3 A lining which has been evaluated in accordance with Resolution A.754(18) to be a "B" (B-0 or B-15, as applicable on basis of the lining test) class lining may be considered forming "continuous 'B' (B-0 or B-15, as applicable) class lining" in conjunction with a "continuous 'B' (B-0 or B-15, as applicable) class ceiling" and with the joining method used in the test (see paragraph 2.2 above) without further testing the lining.

2.4 An enclosed construction installed on an "A" class deck and formed by "continuous 'B' (B-0 or B-15, as applicable) class linings" and "continuous 'B' (B-0 or B-15, as applicable) class ceiling" should be considered forming "continuous 'B' class construction".

PART 04 Test for fire door control systems

Ingangsdatum: 01-07-1998

1 Application

Ingangsdatum: 01-07-1998

Where a control system of fire doors is required to be able to operate in case of fire, the system shall comply with this part.

2 Fire Test Procedures

Ingangsdatum: 01-07-1998

The fire door control systems shall be tested and evaluated in accordance with the test procedure presented in the Appendix to this part.

3 Additional requirements

Ingangsdatum: 01-07-1998

The fire door control systems shall be tested and evaluated in accordance with the test procedure presented in the Appendix to this part.

APPENDIX Fire Test Procedures for fire door control systems

Ingangsdatum: 01-07-1998
01 General
Ingangsdatum: 01-07-1998

1.1 Fire door control systems which are intended to be used for fire doors capable of operating in case of fire shall be tested in accordance with the Fire Test Procedures described in this Appendix independent of its power supply (pneumatical, hydraulic or electrical).

1.2 The fire tests shall be a prototype test and be carried out with the complete control system in a furnace dimensioned according to Resolution A.754(18).

1.3 The construction to be tested shall be, as far as practicable, representative of that to be used on board ships, including the materials and method of assembly.

1.4 The functions of the control system including its closing mechanism shall be tested, i.e. normal functions of and, if required, emergency function, including switchover functions, if this is a basis of the manufacturer's design. The required kind of installation and functions shall be evident from a detailed function description.
02 Nature of prototype control systems
Ingangsdatum: 01-07-1998

2.1 The installation of the prototype control system shall fully comply with the manufacturer's installation manual.

2.2 The prototype control system shall include a typical door arrangement connected to the closing mechanism. For the purpose of the test a door model shall be used. In case of sliding doors, the model door shall run in original door tracks with original supporting and guide rollers. The model door shall have the weight of the largest door to be actuated by this control system.

2.3 In case of pneumatic or hydraulic systems, the actuator (cylinder) shall have the maximum length allowed by the furnace.
03 Materials for prototype control systems

3.1 Specifications
Prior to the test, drawings and the list of materials of the test arrangement shall be submitted to the laboratory by the applicant.

3.2 Control measurements

3.2.1 The testing laboratory shall take reference specimens of all those materials whose characteristics are important to the performance of the prototype control system (excluding steel and equivalent material).

3.2.2 If necessary, non-combustibility tests of insulation material in accordance with part 1 shall be conducted. Adhesives used in the construction of the specimen are not required to be non-combustible, however, they shall have low flame-spread characteristics.

3.2.3 The density of each insulation material shall be determined. The density of mineral wool or any similar compressible material shall be related to the nominal thickness.
Ingangsdatum: 01-07-1998

3.1 Specifications
Prior to the test, drawings and the list of materials of the test arrangement shall be submitted to the laboratory by the applicant.

3.2 Control measurements

3.2.1 The testing laboratory shall take reference specimens of all those materials whose characteristics are important to the performance of the prototype control system (excluding steel and equivalent material).

3.2.2 If necessary, non-combustibility tests of insulation material in accordance with part 1 shall be conducted. Adhesives used in the construction of the specimen are not required to be non-combustible, however, they shall have low flame-spread characteristics.

3.2.3 The density of each insulation material shall be determined. The density of mineral wool or any similar compressible material shall be related to the nominal thickness.
3.1 Specifications
Ingangsdatum: 01-07-1998

Prior to the test, drawings and the list of materials of the test arrangement shall be submitted to the laboratory by the applicant.
3.2 Control measurements
Ingangsdatum: 01-07-1998

3.2.1 The testing laboratory shall take reference specimens of all those materials whose characteristics are important to the performance of the prototype control system (excluding steel and equivalent material).

3.2.2 If necessary, non-combustibility tests of insulation material in accordance with part 1 shall be conducted. Adhesives used in the construction of the specimen are not required to be non-combustible, however, they shall have low flame-spread characteristics.

3.2.3 The density of each insulation material shall be determined. The density of mineral wool or any similar compressible material shall be related to the nominal thickness.

3.2.4 The thickness of each insulation material and combination of materials shall be measured by using a suitable gauge or calipers.
04 Conditioning of the prototype control systems
Ingangsdatum: 01-07-1998

4.1 Conditioning of the prototype control system (except insulation) is not necessary.

4.2 If insulation material is used in the construction, the prototype control system shall not be tested until the insulation has reached an air dry condition. This condition is designed as an equilibrium (constant weight) with an ambient atmosphere of 50% relative humidity at 23°C.

Accelerated conditioning is permissible provided the method does not alter the properties of component materials. High temperature conditioning shall be below temperatures critical for the materials.
05 Mounting of the prototype control systems
Ingangsdatum: 01-07-1998

5.1 The prototype fire door control system and the insulation, if used for protection of the system or parts of it, shall be mounted at the bulkhead plate as shown in figure 1.

5.2 The structural core shall be mounted at the furnace in accordance with the principles for "A" class divisions in paragraph 5 of Resolution A.754(18).

5.3 The door model shall be arranged within the furnace. The structural core to which the system and the door model are fitted shall have no door opening. However, small openings for the release mechanism of the control systems are allowed.

Figure 1 - Structural core for fitting the prototype fire control system
06 Examination of the prototype control systems

6.1 Conformity
The laboratory shall verify the conformity of the prototype control system with the drawings and method of assembly provided by the applicant (see section 2), and any area of discrepancy shall be resolved prior to commencement of the test.

6.2 Operation of the prototype control system Immediately prior to the test, the laboratory shall check the operability of the system by opening the door model by a distance of at least 300 mm. The door model shall then be closed.
Ingangsdatum: 01-07-1998

6.1 Conformity
The laboratory shall verify the conformity of the prototype control system with the drawings and method of assembly provided by the applicant (see section 2), and any area of discrepancy shall be resolved prior to commencement of the test.

6.2 Operation of the prototype control system Immediately prior to the test, the laboratory shall check the operability of the system by opening the door model by a distance of at least 300 mm. The door model shall then be closed.
6.1 Conformity
Ingangsdatum: 01-07-1998

The laboratory shall verify the conformity of the prototype control system with the drawings and method of assembly provided by the applicant (see section 2), and any area of discrepancy shall be resolved prior to commencement of the test.
6.2 Operation of the prototype control system
Ingangsdatum: 01-07-1998

Immediately prior to the test, the laboratory shall check the operability of the system by opening the door model by a distance of at least 300 mm. The door model shall then be closed
07 Instrumentation
Ingangsdatum: 01-07-1998

The furnace and the instrumentation of the furnace shall be in accordance with section 7 of the Annex to Resolution A.754(18).
08 Method of test

8.1 Commencement of test
Not more than 5 min before the commencement of the test, the initial temperatures recorded by all thermocouples shall be checked to ensure consistency and the datum values shall be noted. Similar datum values shall be obtained for deformation, and initial condition of the prototype control system shall be noted.

At the time of the test, the initial average internal temperature shall be 20 ±10°C and shall be within 5°C of the initial ambient temperature.

8.2 Furnace control
The furnace control shall be in accordance with paragraph 8.3 of the Annex to Resolution A.754(18).

8.3 Temperatures, duration of testing and actions during test

8.3.1 The average furnace temperature shall be increased and stabilized at 200° ±50°C within 5 min and kept at the level of 200° ±50°C up to the end of the first 60 min. Then the average furnace temperature shall be increased according to the standard time-temperature curve beginning with the level of 200°C up to 945°C.

8.3.2 The opening and closing function of the door control mechanism shall be activated every 5 min from the beginning of the test for the duration of 60 min.

8.3.3 The automatic switchover shall isolate the door control system from the power supply at the average furnace temperature of 300°C and shall be able to keep the door closed at least up to 945°C.

8.4 Measurements and observations on the prototype control system In case of pneumatic or hydraulic systems, the input pressure which shall be identical with the approved system pressure shall be recorded. Due to a high input pressure, necessary safety precautions shall be taken when the test is carried out.
Ingangsdatum: 01-07-1998

8.1 Commencement of test
Not more than 5 min before the commencement of the test, the initial temperatures recorded by all thermocouples shall be checked to ensure consistency and the datum values shall be noted. Similar datum values shall be obtained for deformation, and initial condition of the prototype control system shall be noted.

At the time of the test, the initial average internal temperature shall be 20 ±10°C and shall be within 5°C of the initial ambient temperature.

8.2 Furnace control
The furnace control shall be in accordance with paragraph 8.3 of the Annex to Resolution A.754(18).

8.3 Temperatures, duration of testing and actions during test

8.3.1 The average furnace temperature shall be increased and stabilized at 200° ±50°C within 5 min and kept at the level of 200° ±50°C up to the end of the first 60 min. Then the average furnace temperature shall be increased according to the standard time-temperature curve beginning with the level of 200°C up to 945°C.

8.3.2 The opening and closing function of the door control mechanism shall be activated every 5 min from the beginning of the test for the duration of 60 min.

8.3.3 The automatic switchover shall isolate the door control system from the power supply at the average furnace temperature of 300°C and shall be able to keep the door closed at least up to 945°C.

8.4 Measurements and observations on the prototype control system In case of pneumatic or hydraulic systems, the input pressure which shall be identical with the approved system pressure shall be recorded. Due to a high input pressure, necessary safety precautions shall be taken when the test is carried out.
8.1 Commencement of test
Ingangsdatum: 01-07-1998

Not more than 5 min before the commencement of the test, the initial temperatures recorded by all thermocouples shall be checked to ensure consistency and the datum values shall be noted. Similar datum values shall be obtained for deformation, and initial condition of the prototype control system shall be noted.

At the time of the test, the initial average internal temperature shall be 20 ±10°C and shall be within 5°C of the initial ambient temperature.
8.2 Furnace control
Ingangsdatum: 01-07-1998

The furnace control shall be in accordance with paragraph 8.3 of the Annex to Resolution A.754(18).
8.3 Temperatures duration of testing and actions during test
Ingangsdatum: 01-07-1998

8.3.1 The average furnace temperature shall be increased and stabilized at 200° ±50°C within 5 min and kept at the level of 200° ±50°C up to the end of the first 60 min. Then the average furnace temperature shall be increased according to the standard time-temperature curve beginning with the level of 200°C up to 945°C.

8.3.2 The opening and closing function of the door control mechanism shall be activated every 5 min from the beginning of the test for the duration of 60 min.

8.3.3 The automatic switchover shall isolate the door control system from the power supply at the average furnace temperature of 300°C and shall be able to keep the door closed at least up to 945°C.
8.4 Measurements and observations on the prototype control system
Ingangsdatum: 01-07-1998

In case of pneumatic or hydraulic systems, the input pressure which shall be identical with the approved system pressure shall be recorded. Due to a high input pressure, necessary safety precautions shall be taken when the test is carried out.
09 Classification criteria
Ingangsdatum: 01-07-1998

9.1 During the first 60 min of the test, a prototype fire door control system shall not fail.

9.2 During the period from the end of the first 60 min until the end of the test, the door shall remain closed.
10 Test report
Ingangsdatum: 01-07-1998

The test report shall include all important information relevant to the prototype control system and the fire test, including the following specific items:

.1 the name of the testing laboratory and the test date;

.2 the name of the applicant for the test;

.3 the name of the manufacturer of the prototype control system and of the products and components used in the construction, together with identification marks and trade names;

.4 the constructional details of the prototype control system, including description and drawings and principal details of components. All the details requested in section 2 shall be given. The description and the drawings which are included in the test report shall, as far as practicable, be based on information derived from a survey of the prototype control system. When full and detailed drawings are not included in the report, then the applicant's drawing(s) of the prototype control system shall be authenticated by the laboratory and at least one copy of the authenticated drawing(s) shall be retained by the laboratory; in this case reference to the applicant's drawing(s) shall be given in the report together with a statement indicating the method of endorsing the drawings;

.5 all the properties of materials used that have a bearing on the fire performance of the prototype control system together with measurements of thickness and density of the insulation material(s);

.6 a statement that the test has been conducted in accordance with the requirements of this
Appendix and if any deviations have been made to the prescribed procedures (including any special requirements of the Administration), a clear statement of the deviations;

.7 the name of the representative of the Administration present at the test. When the test is not witnessed by a representative of the Administration, a note to this effect shall be made in the report in the following form:

"The ... (name of the Administration) was notified of the intention to conduct the test detailed in this report and did not consider it necessary to send a representative to witness it.";

.8 information concerning the location of the pressure gauges or other devices together with tabulated data obtained during the test;

.9 observations of significant behaviour of the prototype control system during test and photographs, if any; and

.10 a statement that the prototype fire door control system has passed the test and complies with the classification criteria.

PART 05 Test for surface flammability

Ingangsdatum: 01-07-1998

1 Application

Ingangsdatum: 01-07-1998

Where a product is required to have a surface with low flame-spread characteristics, the product shall comply with this part.

2 Fire Test Procedures

Ingangsdatum: 01-07-1998

2.1 The surface materials shall be tested and evaluated in accordance with the test procedure specified in Resolution A.653(16). For the purpose of this part, the total heat release value (Qt) for floor coverings given in section 10 of the Annex to Resolution A.653(16) is replaced by =2.0 MJ. The test may be terminated after 40 min.

3 Additional requirements


3.1 Surface materials for bulkheads and ceilings and similar exposed surfaces
In case there is a requirement of maximum gross calorific value (e.g. 45 MJ/m2) for a product, the method specified in standard ISO 1716:1973 is recommended for determining the gross calorific value.

3.2 Floor coverings and primary deck coverings

3.2.1 A primary deck covering is the first layer of a floor construction which is applied directly on top of the deck plating and is inclusive of any primary coat, anti-corrosive compound or adhesive which is necessary to provide protection or adhesion to the deck plating. Other layers in the floor construction above the deck plating are floor coverings.

3.2.2 Where a floor covering is required to be low flame-spread, all layers shall comply with part 5. If the floor covering has a multilayer construction, the Administration may require the tests to be conducted for each layer or for combinations of some layers of the floor coverings. Each layer separately, or a combination of layers (i.e. the test and approval are applicable only to this combination), of the floor covering shall comply with this part. When a primary deck covering is required to be not readily ignitable and is placed below a floor covering, the primary deck covering shall comply with part 6. When the primary deck covering is also the exposed surface, it shall comply with this part. Primer or similar thin film of paint on deck plating need not comply with the above requirements of part 6.

3.3 Combustible ventilation ducts

3.3.1 Where combustible ventilation ducts are required to be of material which has low flame-spread characteristics, the surface flammability test procedure and criteria for lining and ceiling finishes according to Resolution A.653(16) shall be applied for such ducts. In case homogeneous materials are used for the ducts, the test shall apply to outside surface of the duct, whilst both sides of the ducts of composite materials shall be tested.

3.4Insulation materials for cold service systems
Where the exposed surfaces of vapour barriers and adhesives used in conjunction with insulation, as well as insulation of pipe fittings, for cold service systems are required to have low flame-spread characteristics, the surface flammability test procedure and criteria for linings and ceilings according to Resolution A.653(16) shall be applied for such exposed surfaces.

3.5 Other references
Part 2 of this Annex is also applicable to surface materials.
Ingangsdatum: 01-07-1998

3.1 Surface materials for bulkheads and ceilings and similar exposed surfaces
In case there is a requirement of maximum gross calorific value (e.g. 45 MJ/m2) for a product, the method specified in standard ISO 1716:1973 is recommended for determining the gross calorific value.

3.2 Floor coverings and primary deck coverings

3.2.1 A primary deck covering is the first layer of a floor construction which is applied directly on top of the deck plating and is inclusive of any primary coat, anti-corrosive compound or adhesive which is necessary to provide protection or adhesion to the deck plating. Other layers in the floor construction above the deck plating are floor coverings.

3.2.2 Where a floor covering is required to be low flame-spread, all layers shall comply with part 5. If the floor covering has a multilayer construction, the Administration may require the tests to be conducted for each layer or for combinations of some layers of the floor coverings. Each layer separately, or a combination of layers (i.e. the test and approval are applicable only to this combination), of the floor covering shall comply with this part. When a primary deck covering is required to be not readily ignitable and is placed below a floor covering, the primary deck covering shall comply with part 6. When the primary deck covering is also the exposed surface, it shall comply with this part. Primer or similar thin film of paint on deck plating need not comply with the above requirements of part 6.

3.3 Combustible ventilation ducts

3.3.1 Where combustible ventilation ducts are required to be of material which has low flame-spread characteristics, the surface flammability test procedure and criteria for lining and ceiling finishes according to Resolution A.653(16) shall be applied for such ducts. In case homogeneous materials are used for the ducts, the test shall apply to outside surface of the duct, whilst both sides of the ducts of composite materials shall be tested.

3.4Insulation materials for cold service systems
Where the exposed surfaces of vapour barriers and adhesives used in conjunction with insulation, as well as insulation of pipe fittings, for cold service systems are required to have low flame-spread characteristics, the surface flammability test procedure and criteria for linings and ceilings according to Resolution A.653(16) shall be applied for such exposed surfaces.

3.5 Other references
Part 2 of this Annex is also applicable to surface materials.
3.1 Surface materials for bulkheads and ceilings and similar exposed surfaces
Ingangsdatum: 01-07-1998

In case there is a requirement of maximum gross calorific value (e.g. 45 MJ/m2) for a product, the method specified in standard ISO 1716:1973 is recommended for determining the gross calorific value.
3.2 Floor coverings and primary deck coverings
Ingangsdatum: 01-07-1998

3.2.1 A primary deck covering is the first layer of a floor construction which is applied directly on top of the deck plating and is inclusive of any primary coat, anti-corrosive compound or adhesive which is necessary to provide protection or adhesion to the deck plating. Other layers in the floor construction above the deck plating are floor coverings.

3.2.2 Where a floor covering is required to be low flame-spread, all layers shall comply with part 5. If the floor covering has a multilayer construction, the Administration may require the tests to be conducted for each layer or for combinations of some layers of the floor coverings. Each layer separately, or a combination of layers (i.e. the test and approval are applicable only to this combination), of the floor covering shall comply with this part. When a primary deck covering is required to be not readily ignitable and is placed below a floor covering, the primary deck covering shall comply with part 6. When the primary deck covering is also the exposed surface, it shall comply with this part. Primer or similar thin film of paint on deck plating need not comply with the above requirements of part 6.
3.3 Combustible ventilation ducts
Ingangsdatum: 01-07-1998

3.3.1 Where combustible ventilation ducts are required to be of material which has low flame-spread characteristics, the surface flammability test procedure and criteria for lining and ceiling finishes according to Resolution A.653(16) shall be applied for such ducts. In case homogeneous materials are used for the ducts, the test shall apply to outside surface of the duct, whilst both sides of the ducts of composite materials shall be tested.
3.4 Insulation materials for cold service systems
Ingangsdatum: 01-07-1998

Where the exposed surfaces of vapour barriers and adhesives used in conjunction with insulation, as well as insulation of pipe fittings, for cold service systems are required to have low flame-spread characteristics, the surface flammability test procedure and criteria for linings and ceilings according to Resolution A.653(16) shall be applied for such exposed surfaces.
3.5 Other references
Ingangsdatum: 01-07-1998

Part 2 of this Annex is also applicable to surface materials.

APPENDIX Interpretations of results evaluating unusual test specimen behaviour

Ingangsdatum: 01-07-1998
(see paragraph 2.2 of this part)

 

Unusual behaviour

Guidance on classification

1

Flashing, no steady flame

Report furthest progress of flame and time, and whether or not flash is on centerline. Classify on basis of the data.

2

Explosive spalling, no flashing or flame

Accept material as passing test.

3

Rapid flash over surface, later steady flame progress

Report result for both flame fronts but classify on basis of worst performance for each of the four test parameters in the two burning regimes.

4

Specimen or veneer melts and drips off, no flame

Report behaviour and extent of advance on specimen.

5

Explosive spalling, and flame on exposed part of specimen

Report explosions and classify on basis of flame progress irrespective of whether above or below centerline.

6

Specimen or veneer melts, burns and drips off

Reject material regardless of criteria. For floor covering, no more than 10 burning drops are acceptable.

7

Pilot flame extinguished

Report occurrence, reject data and repeat test.

8

Heat release signal after test and re-insertion of dummy specimen remains at a higher or lower level than initial stabilizing level.

Reject data and stabilize the equipment, then repeat test.

9

Very short ignition delay on carpets or non-rigid specimens

Could be caused by pile extension above holder surface, reducing space to pilot flame. Repeat with shims as required by procedure in paragraph 8.1.1 of the Annex to Resolution A.653(16).

10

Specimen breaks up, and falls out of holder

Report behaviour, but classify on basis of worst performance with and without specimen restraint in paragraph 8.3.2 of the Annex to Resolution A.653(16).

11

Substantial jetting combustible pyrolysis gases from specimen, adhesive or bonding agents

Reject material.

12

Small flame remaining along the edge of specimen

Report behaviour and terminate the test 3 min after flaming on exposed surface of specimen ceased.

PART 06 Test for primary deck coverings

Ingangsdatum: 01-07-1998

1 Application

Ingangsdatum: 01-07-1998

1.1 Where the primary deck coverings are required to be not readily ignitable, they shall comply with this part.

2 Fire Test Procedures

Ingangsdatum: 01-07-1998

2.1 The primary deck coverings shall be tested and evaluated in accordance with the Fire Test Procedures specified in Resolution A.687(17).

2.2 The test shall be terminated after 40 min.

3 Additional requirements

Ingangsdatum: 01-07-1998

Part 2 of this Annex 1 is also applicable to primary deck coverings.

PART 07 Test for vertically supported textiles and films

Ingangsdatum: 01-07-1998

1 Application

Ingangsdatum: 01-07-1998

Where draperies, curtains and other supported textile materials are required to have qualities of resistance to the propagation of flame not inferior to those of wool of mass 0.8 kg/m2, they shall comply with this part.

2 Fire Test Procedures

Ingangsdatum: 01-07-1998

The vertically supported textiles and films shall be tested and evaluated in accordance with the Fire Test Procedures specified in Resolution A.471(XII) as amended by Resolution A.563(14)

3 Additional requirements

Ingangsdatum: 01-07-1998

The tests shall be made by using specimens of the final product (e.g. with colour treatment). In cases where only the colours change, a new test is not necessary. However, in cases where the basis product or the treatment procedure change, a new test is required.

PART 08 Test for upholstered furniture

Ingangsdatum: 01-07-1998

1 Application

Ingangsdatum: 01-07-1998

Where upholstered furniture are required to have qualities of resistance to the ignition and propagation of flame, the upholstered furniture shall comply with this part.

2 Fire Test Procedures

Ingangsdatum: 01-07-1998

The upholstered furniture shall be tested and evaluated in accordance with the Fire Test Procedures specified in Resolution A.652(16).

3 Additional requirements

Ingangsdatum: 01-07-1998

The tests shall be made by using specimens of the final product (e.g. with colour treatment). In cases where only the colours change, a new test is not necessary. However, in cases where the basis product or the treatment procedure change, a new test is required.

PART 09 Test for bedding components

Ingangsdatum: 01-07-1998

1 Application

Ingangsdatum: 01-07-1998

Where bedding components are required to have qualities of resistance to the ignition and propagation of flame, the bedding components shall comply with this part.

2 Fire Test Procedures

Ingangsdatum: 01-07-1998

The bedding components shall be tested and evaluated in accordance with the Fire Test Procedures specified in Resolution A.688(17).

3 Additional requirements

Ingangsdatum: 01-07-1998

The tests shall be made by using specimens of the final product (e.g. with colour treatment). In cases where only the colours change, a new test is not necessary. However, in cases where the basis product or the treatment procedure change, a new test is required.

PART 10 Test for fire-restricting materials for high-speed-craft MSC.101(73)

Ingangsdatum: 01-07-2002

1 Application

Ingangsdatum: 01-07-2002

Where materials used in high-speed craft are required to be fire-restricting, they shall comply with this part.

2 Fire test procedures

Ingangsdatum: 01-07-2002

Surface materials on bulkheads, wall and ceiling linings including their supporting structure, furniture, and other structural or interior components required to be fire-restricting materials shall be tested and evaluated in accordance with the fire test procedures specified in resolution MSC.40(64), as amended by resolution MSC.90(71).

PART 11 Test for fire resisting divisions of high-speed-craft MSC.101(73)

Ingangsdatum: 01-07-2002

1 Application

Ingangsdatum: 01-07-2002

Where constructions for use in high-speed craft are required to have fire-resisting properties, they shall comply with this part. Such constructions include fire-resisting bulkheads, decks, ceilings, linings and doors.

2 Fire test procedures

Ingangsdatum: 01-07-2002

Fire-resisting divisions of high-speed craft shall be tested and evaluated in accordance with the fire test procedures specified in resolution MSC.45(65).

3 Additional requirerments

Ingangsdatum: 01-07-2002

3.1 Materials used in fire-resisting divisions shall be non-combustible or fire-restricting as verified in accordance with part 1 or part 10 of this annex, respectively.

3.2 Part 3 of this annex is also applicable to certain constructions such as windows, fire dampers, pipe penetrations and cable transits.

3.3 Part 4 of this annex is also applicable where a control system of fire doors is required to be able to operate in case of fire.

3.4 Where combustible veneers are allowed to be provided in fire-resisting divisions in conjunction with non-combustible substrates, the low flame spread characteristics of such veneers, if required, shall be verified in accordance with part 5 of this annex."

ANNEX 2 Products which may be installed without testing and/or approval

Ingangsdatum: 01-07-1998

01 Non-combustible materials

Ingangsdatum: 01-07-1998

In general, products made only of glass, concrete, ceramic products, natural stone, masonry units, common metals and metal alloys are considered being non-combustible and they may be installed without testing and approval.

02 Materials not generating excessive quantities of smoke nor toxic products in fire

2.1 In general, non-combustible materials are considered to comply with the requirements of part 2 of Annex 1 without further testing. 2.2 In general, surface materials and primary deck coverings with both the total heat release (Qt) of not more than 0.2 MJ and the peak heat release rate (qp) of not more than 1.0 kW (both values determined in accordance with part 5 of Annex 1 or in accordance with Resolution A.653(16) are considered to comply with the requirements of part 2 of Annex 1 without further testing.

Ingangsdatum: 01-07-2002

2.1 In general, non-combustible materials are considered to comply with the requirements of part 2 of Annex 1 without further testing.

2.2 In general, surface materials and primary deck coverings with both the total heat release (Qt ) of not more than 0.2 MJ and the peak heat release rate (qp) of not more than 1.0 kW (both values determined in accordance with part 5 of Annex 1 or in accordance with Resolution A.653(16) are considered to comply with the requirements of part 2 of Annex 1 without further testing.

2.3 For high-speed craft, fire-restricting materials are considered to comply with the requirements of part 2 of annex 1 without further testing." (MSC 101(73)

03 "A", "B" and "F" class divisions

Ingangsdatum: 01-07-1998
3.1 The following products may be installed without testing or approval:

Classification

Product description

Class A-0 bulkhead

A steel bulkhead with dimensions not less than the minimum dimensions given below:

- thickness of plating: 4 mm

- stiffeners 60 x 60 x 5 mm spaced at 600 mm or structural equivalent

Class A-0 deck

A steel deck with dimensions not less than the minimum dimensions given below:

- thickness of plating: 4 mm

- stiffeners 95 x 65 x 7 mm spaced at 600 mm or structural equivalent.

 

3.2 Notwithstanding the provisions in 3.1 above, the materials which are used in "A", "B" and "F" class divisions and which are required to have certain other specified characteristics (e.g. non-combustibility, low flame-spread characteristics, etc.) shall comply with the appropriate parts of Annex 1 or section 8 and Annex 3, of this Code.

04 Fire door control systems

Ingangsdatum: 01-07-1998

(no entries)

05 Low flame-spread surfaces

5.1 Non-combustible materials are considered to comply with the requirements of part 5 of Annex 1. However, due consideration shall be given to the method of application and fixing (e.g. glue). 5.2 Primary deck coverings classified as not readily ignitable in accordance with part 6 of Annex 1 are considered to comply with the requirements of part 5 of Annex 1 for floor coverings.

Ingangsdatum: 01-07-2002

5.1 Non-combustible materials are considered to comply with the requirements of part 5 of Annex 1. However, due consideration shall be given to the method of application and fixing (e.g. glue).

5.2 Primary deck coverings classified as not readily ignitable in accordance with part 6 of Annex 1 are considered to comply with the requirements of part 5 of Annex 1 for floor coverings.

5.3 For high-speed craft, surfaces and materials that are qualified as fire-restricting materials are considered to comply with the requirements of part 5 of annex 1 without further testing." (MSC 101(73)

06 Primary deck coverings

Ingangsdatum: 01-07-1998

Non-combustible materials are considered to comply with the requirements of part 6 of Annex 1. However, due consideration shall be given to the method of application and fixing.

07 Vertically supported textiles and films

Ingangsdatum: 01-07-1998
(no entries)

08 Upholstered furniture

Ingangsdatum: 01-07-1998
(no entries)

09 Bedding components

Ingangsdatum: 01-07-1998
(no entries)

ANNEX 3 Use of other Fire Test Procedures

Ingangsdatum: 01-07-1998
Administrations may use test procedures other than those referred to in Annex 1 as follows:

.1 for Fire Test Procedures previously adopted by the Assembly, the expiry dates are given in the table below; and

.2 for other established test procedures and acceptance criteria applied by an Administration, the test expiry date is 31.12.1998 and the approval expiry date is 31.12.2003.

Products (reference part in Annex 1)

Test procedure

Test expiry date

Approval expiry date

Non-combustible materials (part 1)

Resolution A.472(X11)

31.12.1998

31.12.2003

 

Resolution A.270(VIII)

1.7.1997

1.7.2002

Materials not generating excessive quantities of smoke nor toxic products (part 2)

-

-

-

A, B and F class divisions (part 3)

Resolution A.517(13)*

31.12.1998

31.12.2003

 

Resolution A.163(ES.IV)* as corrected by Resolution A.215(VII)

1.7.1997

1.7.2002

 

Resolution A.163(ES.IV)*

1.7.1997

1.7.2002

Fire door control systems (part 4)

-

-

-

Surface materials (part 5)

Resolution A.564(14)

31.12.1998

31.12.2003

 

Resolution A.516(13)

31.12.1998

31.12.2003

Primary deck coverings (part 6)

Resolution A.214(VII)

31.12.1998

31.12.2003

Vertically supported textiles (part 7)

Resolution A.471(XII)

31.12.1998

31.12.2003

Upholstered furniture (part 8)

-

-

-

Bedding components (part 9)

-

-

-

* The maximum average temperature rise of 140°C may be used instead of 139°C in the acceptance criteria in Resolutions A.163(ES.IV) and A.517(13).


 

Inhoudsopgave

Alles dichtklappenAlles openklappen
Naar boven