Containment of fire
1 Purpose
The purpose of this regulation is to contain a fire in the space of origin. For this purpose, the following functional requirements shall be met:
- the ship shall be subdivided by thermal and structural boundaries;
- thermal insulation of boundaries shall have due regard to the fire risk of the space and adjacent spaces; and
- the fire integrity of the divisions shall be maintained at openings and penetrations.
2 Thermal and structural boundaries
2.1 Thermal and structural subdivision
Ships of all types shall be subdivided into spaces by thermal and structural divisions having regard to the fire risks of the space.
2.2 Passenger ships
2.2.1 Main vertical zones and horizontal zones
2.2.1.1.1 In ships carrying more than 36 passengers, the hull, superstructure and deckhouses shall be subdivided into main vertical zones by "A-60" class divisions. Steps and recesses shall be kept to a minimum, but where they are necessary they shall also be "A-60" class divisions. Where a category (5), (9) or (10) space defined in paragraph 2.2.3.2.2 is on one side or where fuel oil tanks are on both sides of the division the standard may be reduced to "A-0".
2.2.1.1.2 In ships carrying not more than 36 passengers, the hull, superstructure and deckhouses in way of accommodation and service spaces shall be subdivided into main vertical zones by "A" class divisions. These divisions shall have insulation values in accordance with tables in paragraph 2.2.4.
2.2.1.2 As far as practicable, the bulkheads forming the boundaries of the main vertical zones above the bulkhead deck shall be in line with watertight subdivision bulkheads situated immediately below the bulkhead deck. The length and width of main vertical zones may be extended to a maximum of 48 m in order to bring the ends of main vertical zones to coincide with watertight subdivision bulkheads or in order to accommodate a large public space extending for the whole length of the main vertical zone provided that the total area of the main vertical zone is not greater than 1,600 m2 on any deck. The length or width of a main vertical zone is the maximum distance between the furthermost points of the bulkheads bounding it.
2.2.1.3 Such bulkheads shall extend from deck to deck and to the shell or other boundaries.
2.2.1.4 Where a main vertical zone is subdivided by horizontal "A" class divisions into horizontal zones for the purpose of providing an appropriate barrier between a zone with sprinklers and a zone without sprinklers, the divisions shall extend between adjacent main vertical zone bulkheads and to the shell or exterior boundaries of the ship and shall be insulated in accordance with the fire insulation and integrity values given in table 9.4.
2.2.1.5.1 On ships designed for special purposes, such as automobile or railroad car ferries, where the provision of main vertical zone bulkheads would defeat the purpose for which the ship is intended, equivalent means for controlling and limiting a fire shall be substituted and specifically approved by the Administration. Service spaces and ship stores shall not be located on ro-ro decks unless protected in accordance with the applic able regulations.
2.2.1.5.2 However, in a ship with special category spaces, such spaces shall comply with the applicable provisions of regulation 20 and where such compliance would be inconsistent with other requirements for passenger ships specified in this chapter, the requirements of regulation 20 shall prevail.
2.2.2 Bulkheads within a main vertical zone
2.2.2.1 For ships carrying more than 36 passengers, bulkheads which are not required to be "A" class divisions shall be at least "B" class or "C" class divisions as prescribed in the tables in paragraph 2.2.3.
2.2.2.2 For ships carrying not more than 36 passengers, bulkheads within accommodation and service spaces which are not required to be "A" class divisions shall be at least "B" class or "C" class divisions as prescribed in the tables in paragraph 2.2.4. In addition, corridor bulkheads, where not required to be "A" class, shall be "B" class divisions which shall extend from deck to deck except:
- when continuous "B" class ceilings or linings are fitted on both sides of the bulkhead, the portion of the bulkhead behind the continuous ceiling or lining shall be of material which, in thickness and composition, is acceptable in the construction of "B" class divisions, but which shall be required to meet "B" class integrity standards only in so far as is reasonable and practicable in the opinion of the Administration; and
- in the case of a ship protected by an automatic sprinkler system complying with the provisions of the Fire Safety Systems Code, the corridor bulkheads may terminate at a ceiling in the corridor provided such bulkheads and ceilings are of “B” class standard in compliance with paragraph 2.2.4. All doors and frames in such bulkheads shall be of non-combustible materials and shall have the same fire integrity as the bulkhead in which they are fitted.
2.2.2.3 Bulkheads required to be "B" class divisions, except corridor bulkheads as prescribed in paragraph 2.2.2.2, shall extend from deck to deck and to the shell or other boundaries. However, where a continuous "B" class ceiling or lining is fitted on both sides of a bulkhead which is at least of the same fire resistance as the adjoining bulkhead, the bulkhead may terminate at the continuous ceiling or lining.
2.2.3 Fire integrity of bulkheads and decks in ships carrying more than 36 passengers
2.2.3.1 In addition to complying with the specific provisions for fire integrity of bulkheads and decks of passenger ships, the minimum fire integrity of all bulkheads and decks shall be as prescribed in tables 9.1 and 9.2. Where, due to any particular structural arrangements in the ship, difficulty is experienced in determining from the tables the minimum fire integrity value of any divisions, such values shall be determined to the satisfaction of the Administration.
2.2.3.2 The following requirements shall govern application of the tables:
- Table 9.1 shall apply to bulkheads not bounding either main vertical zones or horizontal zones. Table 9.2 shall apply to decks not forming steps in main vertical zones nor bounding horizontal zones;
- For determining the appropriate fire integrity standards to be applied to boundaries between adjacent spaces, such spaces are classified according to their fire risk as shown in categories (1) to (14) below. Where the contents and use of a space are such that there is a doubt as to its classification for the purpose of this regulation, or where it is possible to assign two or more classifications to a space, it shall be treated as a space within the relevant category having the most stringent boundary requirements. Smaller, enclosed rooms within a space that have less than 30% communicating openings to that space are considered separate spaces.
The fire integrity of the boundary bulkheads and decks of such smaller rooms shall be as prescribed in tables 9.1 and 9.2. The title of each category is intended to be typical rather than restrictive. The number in parentheses preceding each category refers to the applicable column or row in the tables.
- Control stations
Spaces containing emergency sources of power and lighting.
Wheelhouse and chartroom.
Spaces containing the ship’s radio equipment.
Fire control stations
Control room for propulsion machinery when located outside the propulsion machinery space.
Spaces containing centralized fire alarm equipment.
Spaces containing centralized emergency public address system stations and equipment.
- Stairways
Interior stairways, lifts, totally enclosed emergency escape trunks, and escalators (other than those wholly contained within the machinery spaces) for passengers and crew and enclosures thereto.
In this connection a stairway which is enclosed at only one level shall be regarded as part of the space from which it is not separated by a fire door.
- Corridors
Passenger and crew corridors and lobbies.
- Evacuation stations and external escape routes
Survival craft stowage area.
Open deck spaces and enclosed promenades forming lifeboat and liferaft embarkation and lowering stations.
Assembly stations, internal and external.
External stairs and open decks used for escape routes.
The ship’s side to the waterline in the lightest seagoing condition, superstructure and deckhouse sides situated below and adjacent to the liferaft and evacuation slide embarkation areas.
- Open deck spaces
Open deck spaces and enclosed promenades clear of lifeboat and liferaft embarkation and lowering stations. To be considered in this category, enclosed promenades shall have no significant fire risk, meaning that furnishings shall be restricted to deck furniture. In addition, such spaces shall be naturally ventilated by permanent openings.
Air spaces (the space outside superstructures and deckhouses).
- Accommodation spaces of minor fire risk
Cabins containing furniture and furnishings of restricted fire risk.
Offices and dispensaries containing furniture and furnishings of restricted fire risk.
Public spaces containing furniture and furnishings of restricted fire risk and having a deck area of less than 50 m2.
- Accommodation spaces of moderate fire risk
Spaces as in category (6) above but containing furniture and furnishings of other than restricted fire risk.
Public spaces containing furniture and furnishings of restricted fire risk and having a deck area of 50 m2 or more.
Isolated lockers and small store-rooms in accommodation spaces having areas less than 4 m2 (in which flammable liquids are not stowed).
Sale shops. Motion picture projection and film stowage rooms. Diet kitchens (containing no open flame).
Cleaning gear lockers (in which flammable liquids are not stowed).
Laboratories (in which flammable liquids are not stowed).
Pharmacies.
Small drying rooms (having a deck area of 4 m2 or less).
Specie rooms.
Operating rooms.
- Accommodation spaces of greater fire risk
Public spaces containing furniture and furnishings of other than restricted fire risk and having a deck area of 50 m2 or more.
Barber shops and beauty parlours.
Saunas.
- Sanitary and similar spaces
Communal sanitary facilities, showers, baths, water closets, etc.
Small laundry rooms.
Indoor swimming pool area.
Isolated pantries containing no cooking appliances in accommodation spaces.
Private sanitary facilities shall be considered a portion of the space in which they are located.
- Tanks, voids and auxiliary machinery spaces having little or no fire risk
Water tanks forming part of the ship’s structure.
Voids and cofferdams.
Auxiliary machinery spaces which do not contain machinery having a pressure lubrication system and where storage of combustibles is prohibited, such as:
- ventilation and air-conditioning rooms;
- windlass room;
- steering gear room;
- stabilizer equipment room;
- electrical propulsion motor room;
rooms containing section switchboards and purely electrical equipment other than oil-filled electrical transformers (above 10 kVA);
shaft alleys and pipe tunnels;
spaces for pumps and refrigeration machinery (not handling or using flammable liquids).
Closed trunks serving the spaces listed above.
Other closed trunks such as pipe and cable trunks.
- Auxiliary machinery spaces, cargo spaces, cargo and other oil tanks and other similar spaces of moderate fire risk
Cargo oil tanks.
Cargo holds, trunkways and hatchways.
Refrigerated chambers.
Oil fuel tanks (where installed in a separate space with no machinery).
Shaft alleys and pipe tunnels allowing storage of combustibles.
Auxiliary machinery spaces as in category (10) which contain machinery having a pressure lubrication system or where storage of combustibles is permitted.
Oil fuel filling stations.
Spaces containing oil-filled electrical transformers (above 10 kVA).
Spaces containing turbine and reciprocating steam engine driven auxiliary generators and small internal combustion engines of power output up to 110 kW driving generators, sprinkler, drencher or fire pumps, bilge pumps, etc.
Closed trunks serving the spaces listed above.
- Machinery spaces and main galleys
Main propulsion machinery rooms (other than electric propulsion motor rooms) and boiler rooms.
Auxiliary machinery spaces other than those in categories (10) and (11) which contain internal combustion machinery or other oil-burning, heating or pumping units.
Main galleys and annexes.
Trunks and casings to the spaces listed above.
- Store-rooms, workshops, pantries, etc.
Main pantries not annexed to galleys.
Main laundry.
Large drying rooms (having a deck area of more than 4 m2)
Miscellaneous stores.
Mail and baggage rooms.
Garbage rooms.
Workshops (not part of machinery spaces, galleys, etc.).
Lockers and store-rooms having areas greater than 4 m2, other than those spaces that have provisions for the storage of flammable liquids.
- Other spaces in which flammable liquids are stowed Paint lockers.
Store-rooms containing flammable liquids (including dyes, medicines, etc.).
Laboratories (in which flammable liquids are stowed);
- Where a single value is shown for the fire integrity of a boundary between two spaces, that value shall apply in all cases;
- Notwithstanding the provisions of paragraph 2.2.2 there are no special requirements for material or integrity of boundaries where only a dash appears in the tables; and
- The Administration shall determine in respect of category (5) spaces whether the insulation values in table 9.1 shall apply to ends of deckhouses and superstructures, and whether the insulation values in table 9.2 shall apply to weather decks. In no case shall the requirements of category (5) of tables 9.1 or 9.2 necessitate enclosure of spaces which in the opinion of the Administration need not be enclosed.
Table 9.1 – Bulkheads not bounding either main vertical zones or horizontal zones
Spaces | | (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | (10) | (11) | (12) | (13) | (14) |
Control stations | (1) | B-0a | A-0 | A-0 | A-0 | A-0 | A-60 | A-60 | A-60 | A-0 | A-0 | A-60 | A-60 | A-60 | A-60 |
Stairways | (2) | | A-0a | A-0 | A-0 | A-0 | A-0 | A-15 | A-15 | A-0c | A-0 | A-15 | A-30 | A-15 | A-30 |
Corridors | (3) | | | B-15 | A-60 | A-0 | B-15 | B-15 | B-15 | B-15 | A-0 | A-15 | A-30 | A-0 | A-30 |
Evacuation stations and external escape routes | (4) | | | | | A-0 | A-60b,d | A-60b,d | A-60b,d | A-0d | A-0 | A-60b | A-60b | A-60b | A-60b |
Open deck spaces | (5) | | | | | | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 |
Accommodation spaces of minor fire risk | (6) | | | | | | B-0 | B-0 | B-0 | C | A-0 | A-0 | A-30 | A-0 | A-30 |
Accommodation spaces of moderate fire risk | (7) | | | | | | | B-0 | B-0 | C | A-0 | A-15 | A-60 | A-15 | A-60 |
Accommodation spaces of greater fire risk | (8) | | | | | | | | B-0 | C | A-0 | A-30 | A-60 | A-15 | A-60 |
Sanitary and similar spaces | (9) | | | | | | | | | C | A-0 | A-0 | A-0 | A-0 | A-0 |
Tanks, voids and auxiliary machinery spaces having little or no fire risk | (10) | | | | | | | | | | A-0a | A-0 | A-0 | A-0 | A-0 |
Auxiliary machinery spaces, cargo spaces, cargo and other oil tanks and other similar spaces ofmoderate fire risk | (11) | | | | | | | | | | | A-0a | A-0 | A-0 | A-15 |
Machinery spaces and main galleys | (12) | | | | | | | | | | | | A-0a | A-0 | A-60 |
Store-rooms, workshops, pantries, etc. | (13) | | | | | | | | | | | | | A-0a | A-0 |
Other spaces in which flammableliquids are stowed | (14) | | | | | | | | | | | | | | A-30 |
See notes following table 9.2.
Table 9.2 – Decks not forming steps in main vertical zones nor bounding horizontal zones
| | (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | (10) | (11) | (12) | (13) | (14) |
Control stations | (1) | A-30 | A-30 | A-15 | A-0 | A-0 | A-0 | A-15 | A-30 | A-0 | A-0 | A-0 | A-60 | A-0 | A-60 |
Stairways | (2) | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-30 | A-0 | A-30 |
Corridors | (3) | A-15 | A-0 | A-0a | A-60 | A-0 | A-0 | A-15 | A-15 | A-0 | A-0 | A-0 | A-30 | A-0 | A-30 |
Evacuation stations and external escape routes | (4) | A-0 | A-0 | A-0 | A-0 | - | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 |
Open deck spaces | (5) | A-0 | A-0 | A-0 | A-0 | - | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 |
Accommodation spaces of minor fire risk | (6) | A-60 | A-15 | A-0 | A-60 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 |
Accommodation spaces of moderate fire risk | (7) | A-60 | A-15 | A-15 | A-60 | A-0 | A-0 | A-15 | A-15 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 |
Accommodation spaces of greater fire risk | (8) | A-60 | A-15 | A-15 | A-60 | A-0 | A-15 | A-15 | A-30 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 |
Sanitary and similar spaces | (9) | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 |
Tanks, voids and auxiliary machinery spaces having little or no fire risk | (10) | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0a | A-0 | A-0 | A-0 | A-0 |
Auxiliary machinery spaces, cargo spaces, cargo and other oil tanks and other similar spaces ofmoderate fire risk | (11) | A-60 | A-60 | A-60 | A-60 | A-0 | A-0 | A-15 | A-30 | A-0 | A-0 | A-0a | A-0 | A-0 | A-30 |
Machinery spaces and main galleys | (12) | A-60 | A-60 | A-60 | A-60 | A-0 | A-60 | A-60 | A-60 | A-0 | A-0 | A-30 | A-30a | A-0 | A-60 |
Store-rooms, workshops, pantries, etc. | (13) | A-60 | A-30 | A-15 | A-60 | A-0 | A-15 | A-30 | A-30 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 |
Other spaces in which flammableliquids are stowed | (14) | A-60 | A-60 | A-60 | A-60 | A-0 | A-30 | A-60 | A-60 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 |
Note: To be applied to tables 9.1 and 9.2.
- Where adjacent spaces are in the same numerical category and superscript "a" appears, a bulkhead or deck between such spaces need not be fitted if deemed unnecessary by the Administration. For example, in category (12) a bulkhead need not be required between a galley and its annexed pantries provided the pantry bulkhead and decks maintain the integrity of the galley boundaries. A bulkhead is, however, required between a galley and machinery space even though both spaces are in category (12).
- The ship’s side, to the waterline in the lightest seagoing condition, superstructure and deckhouse sides situated below and adjacent to liferafts and evacuation slides may be reduced to "A-30".
- Where public toilets are installed completely within the stairway enclosure, the public toilet bulkhead within the stairway enclosure can be of "B" class integrity.
- Where spaces of categories (6), (7), (8) and (9) are located completely within the outer perimeter of the assembly station, the bulkheads of these spaces are allowed to be of "B-0" class integrity. Control positions for audio, video and light installations may be considered as part of the assembly station.
2.2.3.3 Continuous "B" class ceilings or linings, in association with the relevant decks or bulkheads, may be accepted as contributing wholly or in part, to the required insulation and integrity of a division.
2.2.3.4 Construction and arrangement of saunas
2.2.3.4.1 The perimeter of the sauna shall be of "A" class boundaries and may include changing rooms, showers and toilets. The sauna shall be insulated to A-60 standard against other spaces except those inside of the perimeter and spaces of categories (5), (9) and (10).
2.2.3.4.2 Bathrooms with direct access to saunas may be considered as part of them. In such cases, the door between sauna and the bathroom need not comply with fire safety requirements.
2.2.3.4.3 The traditional wooden lining on the bulkheads and ceiling are permitted in the sauna. The ceiling above the oven shall be lined with a non-combustible plate with an air gap of at least 30 mm. The distance from the hot surfaces to combustible materials shall be at least 500 mm or the combustible materials shall be protected (e.g. non-combustible plate with an air gap of at least 30 mm).
2.2.3.4.4 The traditional wooden benches are permitted to be used in the sauna.
2.2.3.4.5 The sauna door shall open outwards by pushing.
2.2.3.4.6 Electrically heated ovens shall be provided with a timer.
2.2.4 Fire integrity of bulkheads and decks in ships carrying not more than 36 passengers
2.2.4.1 In addition to complying with the specific provisions for fire integrity of bulkheads and decks of passenger ships, the minimum fire integrity of bulkheads and decks shall be as prescribed in tables 9.3 and 9.4.
2.2.4.2 The following requirements govern application of the tables:
- Tables 9.3 and 9.4 shall apply respectively to the bulkheads and decks separating adjacent spaces;
- For determining the appropriate fire integrity standards to be applied to divisions between adjacent spaces, such spaces are classified according to their fire risk as shown in categories (1) to (11) below. Where the contents and use of a space are such that there is a doubt as to its classification for the purpose of this regulation, or where it is possible to assign two or more classifications to a space, it shall be treated as a space within the relevant category having the most stringent boundary requirements. Smaller, enclosed rooms within a space that have less than 30 % communicating openings to that space are considered separate spaces. The fire integrity of the boundary bulkheads and decks of such smaller rooms shall be as prescribed in tables 9.3 and 9.4. The title of each category is intended to be typical rather than restrictive. The number in parentheses preceding each category refers to the applicable column or row in the tables.
- Control stations
Spaces containing emergency sources of power and lighting.
Wheelhouse and chartroom.
Spaces containing the ship’s radio equipment.
Fire control stations.
Control room for propulsion machinery when located outside the machinery space.
Spaces containing centralized fire alarm equipment.
- Corridors
Passenger and crew corridors and lobbies.
- Accommodation spaces
Spaces as defined in regulation 3.1 excluding corridors.
- Stairways
Interior stairways, lifts, totally enclosed emergency escape trunks, and escalators (other than those wholly contained within the machinery spaces) and enclosures thereto.
In this connection, a stairway which is enclosed only at one level shall be regarded as part of the space from which it is not separated by a fire door.
- Service spaces (low risk)
Lockers and store-rooms not having provisions for the storage of flammable liquids and having areas less than 4 m2 and drying rooms and laundries.
- Machinery spaces of category A
Spaces as defined in regulation 3.31.
- Other machinery spaces
Electrical equipment rooms (auto-telephone exchange, air-conditioning duct spaces).
Spaces as defined in regulation 3.30 excluding machinery spaces of category A.
- Cargo spaces
All spaces used for cargo (including cargo oil tanks) and trunkways and hatchways to such spaces, other than special category spaces.
- Service spaces (high risk)
Galleys, pantries containing cooking appliances, paint and lamp rooms, lockers and store-rooms having areas of 4 m2 or more, spaces for the storage of flammable liquids, saunas and workshops other than those forming part of the machinery spaces.
- Open decks
Open deck spaces and enclosed promenades having little or no fire risk. Enclosed promenades should have no significant fire risk, meaning that furnishing should be restricted to deck furniture. In addition, such spaces should be naturally ventilated by permanent openings. Air spaces (the space outside superstructures and deckhouses).
- Special category and ro-ro spaces
Spaces as defined in regulations 3.41 and 3.46;
- In determining the applicable fire integrity standard of a boundary between two spaces within a main vertical zone or horizontal zone which is not protected by an automatic sprinkler system complying with the provisions of the Fire Safety Systems Code or between such zones neither of which is so protected, the higher of the two values given in the tables shall apply; and
- In determining the applicable fire integrity standard of a boundary between two spaces within a main vertical zone or horizontal zone which is protected by an automatic sprinkler system complying with the provisions of the Fire Safety Systems Code or between such zones both of which are so protected, the lesser of the two values given in the tables shall apply. Where a zone with sprinklers and a zone without sprinklers meet within accommodation and service spaces, the higher of the two values given in the tables shall apply to the division between the zones.
2.2.4.3 Continuous "B" class ceilings or linings, in association with the relevant decks or bulkheads, may be accepted as contributing, wholly or in part, to the required insulation and integrity of a division.
2.2.4.4 External boundaries which are required in regulation 11.2 to be of steel or other equivalent material may be pierced for the fitting of windows and sidescuttles provided that there is no requirement for such boundaries of passenger ships to have "A" class integrity. Similarly, in such boundaries which are not required to have "A" class integrity, doors may be constructed of materials which are to the satisfaction of the Administration.
2.2.4.5 Saunas shall comply with paragraph 2.2.3.4.
Table 9.3 – Fire integrity of bulkheads separating adjacent spaces
Spaces | | (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | (10) | (11) |
Control stations | (1) | A-0c | A-0 | A-60 | A-0 | A-15 | A-60 | A-15 | A-60 | A-60 | * | A-60 |
Corridors | (2) | | Ce | B-0e | A-0aB-0e | B-0e | A-60 | A-0 | A-0 | A-15A-0d | * | A-15 |
Accommodation spaces | (3) | | | Ce | A-0aB-0e | B-0e | A-60 | A-0 | A-0 | A-15A-0d | * | A-30A-0d |
Stairways | (4) | | | | A-0aB-0e | A-0aB-0e | A-60 | A-0 | A-0 | A-15A-0d | * | A-15 |
Service spaces (low risk) | (5) | | | | | Ce | A-60 | A-0 | A-0 | A-0 | * | A-0 |
Machinery spaces of category A | (6) | | | | | | * | A-0 | A-0 | A-60 | * | A-60 |
Other machinery spaces | (7) | | | | | | | A-0b | A-0 | A-0 | * | A-0 |
Cargo spaces | (8) | | | | | | | | * | A-0 | * | A-0 |
Service spaces (high risk) | (9) | | | | | | | | | A-0b | * | A-30 |
Open decks | (10) | | | | | | | | | | | A-0 |
Special category and ro-ro spaces | (11) | | | | | | | | | | | A-0 |
Table 9.4 – Fire integrity of decks separating adjacent spaces
| | (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | (10) | (11) |
Control stations | (1) | A-0 | A-0 | A-0 | A-0 | A-0 | A-60 | A-0 | A-0 | A-0 | * | A-30 |
Corridors | (2) | A-0 | * | * | A-0 | * | A-60 | A-0 | A-0 | A-0 | * | A-0 |
Accommodationspaces | (3) | A-60 | A-0 | * | A-0 | * | A-60 | A-0 | A-0 | A-0 | * | A-30A-0d |
Stairways | (4) | A-0 | A-0 | A-0 | * | A-0 | A-60 | A-0 | A-0 | A-0 | * | A-0 |
Service spaces (low risk) | (5) | A-15 | A-0 | A-0 | A-0 | * | A-60 | A-0 | A-0 | A-0 | * | A-0 |
Machinery spaces of category A | (6) | A-60 | A-60 | A-60 | A-60 | A-60 | * | A-60f | A-30 | A-60 | * | A-60 |
Other machinery spaces | (7) | A-15 | A-0 | A-0 | A-0 | A-0 | A-0 | * | A-0 | A-0 | * | A-0 |
Cargo spaces | (8) | A-60 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | * | A-0 | * | A-0 |
Service spaces (high risk) | (9) | A-60 | A-30A-0d | A-30A-0d | A-30A-0d | A-0 | A-60 | A-0 | A-0 | A-0 | * | A-30 |
Open decks | (10) | * | * | * | * | * | * | * | * | * | - | A-0 |
Special category and ro-ro spaces | (11) | A-60 | A-15 | A-30A-0d | A-15 | A-0 | A-30 | A-0 | A-0 | A-30 | A-0 | A-0 |
Notes: To be applied to both tables 9.3 and 9.4 as appropriate.
- For clarification as to which applies, see paragraphs 2.2.2 and 2.2.5.
- Where spaces are of the same numerical category and superscript b appears, a bulkhead or deck of the rating shown in the tables is only required when the adjacent spaces are for a different purpose, (e.g. in category (9)). A galley next to a galley does not require a bulkhead but a galley next to a paint room requires an "A-0" bulkhead.
- Bulkhead separating the wheelhouse and chartroom from each other may have a "B-0" rating.
- See paragraphs 2.2.4.2.3 and 2.2.4.2.4.
- For the application of paragraph 2.2.1.1.2, "B-0" and "C", where appearing in table 9.3,
shall be read as "A-0".
- Fire insulation need not be fitted if the machinery space in category (7), in the opinion of the Administration, has little or no fire risk.
* Where an asterisk appears in the tables, the division is required to be of steel or other equivalent material, but is not required to be of "A" class standard. However, where a deck, except in a category (10) space, is penetrated for the passage of electric cables, pipes and vent ducts, such penetrations should be made tight to prevent the passage of flame and smoke. Divisions between control stations (emergency generators) and open decks may have air intake openings without means for closure, unless a fixed gas fire-fighting system is fitted. For the application of paragraph 2.2.1.1.2, an asterisk, where appearing in table 9.4, except for categories (8) and (10), shall be read as “A-0”.
2.2.5 Protection of stairways and lifts in accommodation area
2.2.5.1 Stairways shall be within enclosures formed of "A" class divisions, with positive means of closure at all openings, except that:
- a stairway connecting only two decks need not be enclosed, provided the integrity of the deck is maintained by proper bulkheads or self-closing doors in one 'tween-deck space. When a stairway is closed in one 'tween-deck space, the stairway enclosure shall be protected in accordance with the tables for decks in paragraphs 2.2.3 or 2.2.4; and
- stairways may be fitted in the open in a public space, provided they lie wholly within the public space.
2.2.5.2 Lift trunks shall be so fitted as to prevent the passage of smoke and flame from one ‘tween-deck to another and shall be provided with means of closing so as to permit the control of draught and smoke. Machinery for lifts located within stairway enclosures shall be arranged in a separate room, surrounded by steel boundaries, except that small passages for lift cables are permitted. Lifts which open into spaces other than corridors, public spaces, special category spaces, stairways and external areas shall not open into stairways included in the means of escape.
2.3 Cargo ships except tankers
2.3.1 Methods of protection in accommodation area
2.3.1.1 One of the following methods of protection shall be adopted in accommodation and service spaces and control stations:
- Method IC
The construction of internal divisional bulkheads of non-combustible "B" or "C" class divisions generally without the installation of an automatic sprinkler, fire detection and fire alarm system in the accommodation and service spaces, except as required by regulation 7.5.5.1; or
- Method IIC
The fitting of an automatic sprinkler, fire detection and fire alarm system as required by regulation 7.5.5.2 for the detection and extinction of fire in all spaces in which fire might be expected to originate, generally with no restriction on the type of internal divisional bulkheads; or
- Method IIIC
The fitting of a fixed fire detection and fire alarm system as required by regulation 7.5.5.3, in spaces in which a fire might be expected to originate, generally with no restriction on the type of internal divisional bulkheads, except that in no case must the area of any accommodation space or spaces bounded by an "A" or "B" class division exceed 50 m2. Consideration may be given by the Administration to increasing this area for public spaces.
2.3.1.2 The requirements for the use of non-combustible materials in the construction and insulation of boundary bulkheads of machinery spaces, control stations, service spaces, etc., and the protection of the above stairway enclosures and corridors will be common to all three methods outlined in paragraph 2.3.1.1.
2.3.2 Bulkheads within accommodation area
2.3.2.1 Bulkheads required to be "B" class divisions shall extend from deck to deck and to the shell or other boundaries. However, where a continuous "B" class ceiling or lining is fitted on both sides of the bulkhead, the bulkhead may terminate at the continuous ceiling or lining.
2.3.2.2 Method IC
Bulkheads not required by this or other regulations for cargo ships to be "A" or "B" class divisions, shall be of at least "C" class construction.
2.3.2.3 Method IIC
There shall be no restriction on the construction of bulkheads not required by this or other regulations for cargo ships to be "A" or "B" class divisions except in individual cases where "C" class bulkheads are required in accordance with table 9.5.
2.3.2.4 Method IIIC
There shall be no restriction on the construction of bulkheads not required for cargo ships to be "A" or "B" class divisions except that the area of any accommodation space or spaces bounded by a continuous "A" or "B" class division must in no case exceed 50 m2, except in individual cases where "C" class bulkheads are required in accordance with table 9.5. Consideration may be given by the Administration to increasing this area for public spaces.
2.3.3 Fire integrity of bulkheads and decks
2.3.3.1 In addition to complying with the specific provisions for fire integrity of bulkheads and decks of cargo ships, the minimum fire integrity of bulkheads and decks shall be as prescribed in tables 9.5 and 9.6.
2.3.3.2 The following requirements shall govern application of the tables:
- Tables 9.5 and 9.6 shall apply respectively to the bulkheads and decks separating adjacent spaces;
- For determining the appropriate fire integrity standards to be applied to divisions between adjacent spaces, such spaces are classified according to their fire risk as shown in categories (1) to (11) below. Where the contents and use of a space are such that there is a doubt as to its classification for the purpose of this regulation, or where it is possible to assign two or more classifications to a space, it shall be treated as a space within the relevant category having the most stringent boundary requirements. Smaller, enclosed rooms within a space that have less than 30% communicating openings to that space are considered separate spaces. The fire integrity of the boundary bulkheads and decks of such smaller rooms shall be as prescribed in tables 9.5 and 9.6. The title of each category is intended to be typical rather than restrictive. The number in parentheses preceding each category refers to the applicable column or row in the tables;
- Control stations
Spaces containing emergency sources of power and lighting.
Wheelhouse and chartroom.
Spaces containing the ship’s radio equipment.
Fire control stations.
Control room for propulsion machinery when located outside the machinery space.
Spaces containing centralized fire alarm equipment.
- Corridors
corridors and lobbies.
- Accommodation spaces
Spaces as defined in regulation 3.1, excluding corridors.
- Stairways
Interior stairway, lifts, totally enclosed emergency escape trunks, and escalators (other than those wholly contained within the machinery spaces) and enclosures thereto.
In this connection, a stairway which is enclosed only at one level shall be regarded as part of the space from which it is not separated by a fire door.
- Service spaces (low risk)
Lockers and store-rooms not having provisions for the storage of flammable liquids and having areas less than 4 m2 and drying rooms and laundries.
- Machinery spaces of category A
Spaces as defined in regulation 3.31.
- Other machinery spaces
Electrical equipment rooms (auto-telephone exchange, air-conditioning duct spaces).
Spaces as defined in regulation 3.30 excluding machinery spaces of category A.
- Cargo spaces
All spaces used for cargo (including cargo oil tanks) and trunkways and hatchways to such spaces.
- Service spaces (high risk)
Galleys, pantries containing cooking appliances, saunas, paint lockers and store-rooms having areas of 4 m2 or more, spaces for the storage of flammable liquids, and workshops other than those forming part of the machinery spaces.
- Open decks
Open deck spaces and enclosed promenades having little or no fire risk. To be considered in this category, enclosed promenades shall have no significant fire risk, meaning that furnishings shall be restricted to deck furniture. In addition, such spaces shall be naturally ventilated by permanent openings.
Air spaces (the space outside superstructures and deckhouses).
- Ro-ro and vehicle spaces
Ro-ro spaces as defined in regulation 3.41.
Vehicle spaces as defined in regulation 3.49.
Table 9.5 – Fire integrity of bulkheads separating adjacent spaces
Spaces | | (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | (10) | (11) |
Control stations | (1) | A-0e | A-0 | A-60 | A-0 | A-15 | A-60 | A-15 | A-60 | A-60 | * | A-60 |
Corridors | (2) | | C | B-0 | B-0A-0c | B-0 | A-60 | A-0 | A-0 | A-0 | * | A-30 |
Accommodationspaces | (3) | | | Ca, b | B-0A-0c | B-0 | A-60 | A-0 | A-0 | A-0 | * | A-30 |
Stairways | (4) | | | | B-0A-0c | B-0A-0c | A-60 | A-0 | A-0 | A-0 | * | A-30 |
Service spaces (low risk) | (5) | | | | | C | A-60 | A-0 | A-0 | A-0 | * | A-0 |
Machinery spaces of category A | (6) | | | | | | * | A-0 | A-0g | A-60 | * | A-60f |
Other machinery spaces | (7) | | | | | | | A-0d | A-0 | A-0 | * | A-0 |
Cargo spaces | (8) | | | | | | | | * | A-0 | * | A-0 |
Service spaces (high risk) | (9) | | | | | | | | | A-0d | * | A-30 |
Open decks | (10) | | | | | | | | | | - | A-0 |
Ro-ro and vehicle spaces | (11) | | | | | | | | | | | *h |
Table 9.6 – Fire integrity of decks separating adjacent spaces
| | (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | (10) | (11) |
Control stations | (1) | A-0 | A-0 | A-0 | A-0 | A-0 | A-60 | A-0 | A-0 | A-0 | * | A-60 |
Corridors | (2) | A-0 | * | * | A-0 | * | A-60 | A-0 | A-0 | A-0 | * | A-30 |
Accommodationspaces | (3) | A-60 | A-0 | * | A-0 | * | A-60 | A-0 | A-0 | A-0 | * | A-30 |
Stairways | (4) | A-0 | A-0 | A-0 | * | A-0 | A-60 | A-0 | A-0 | A-0 | * | A-30 |
Service spaces (low risk) | (5) | A-15 | A-0 | A-0 | A-0 | * | A-60 | A-0 | A-0 | A-0 | * | A-0 |
Machinery spaces of category A | (6) | A-60 | A-60 | A-60 | A-60 | A-60 | * | A-60i | A-30 | A-60 | * | A-60 |
Other machinery spaces | (7) | A-15 | A-0 | A-0 | A-0 | A-0 | A-0 | * | A-0 | A-0 | * | A-0 |
Cargo spaces | (8) | A-60 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | * | A-0 | * | A-0 |
Service spaces (high risk) | (9) | A-60 | A-0 | A-0 | A-0 | A-0 | A-60 | A-0 | A-0 | A-0d | * | A-30 |
Open decks | (10) | * | * | * | * | * | * | * | * | * | - | A-0 |
Special category and ro-ro spaces | (11) | A-60 | A-30 | A-30 | A-30 | A-0 | A-60 | A-0 | A-0 | A-30 | * | *h |
Note: To be applied to tables 9.5 and 9.6 as appropriate.
- No special requirements are imposed upon bulkheads in methods IIC and IIIC fire protection.
- In case of method IIIC "B" class bulkheads of "B-0" rating shall be provided between spaces or groups of spaces of 50 m2 and over in area.
- For clarification as to which applies, see paragraphs 2.3.2 and 2.3.4.
- Where spaces are of the same numerical category and superscript d appear, a bulkhead or deck of the rating shown in the tables is only required when the adjacent spaces are for a different purpose (e.g. in category (9)). A galley next to a galley does not require a bulkhead but a galley next to a paint room requires an "A-0" bulkhead.
- Bulkheads separating the wheelhouse, chartroom and radio room from each other may have a "B-0" rating.
- An "A-0" rating may be used if no dangerous goods are intended to be carried or if such goods are stowed not less than 3 m horizontally from such a bulkhead.
- For cargo spaces in which dangerous goods are intended to be carried, regulation 19.3.8 applies.
- Bulkheads and decks separating ro-ro spaces shall be capable of being closed reasonably gastight and such divisions shall have "A" class integrity in so far as reasonable and practicable, if in the opinion of the Administration it has little or no fire risk.
- Fire insulation need not be fitted if the machinery in category (7) if, in the opinion of the Administration, it has little or no fire risk.
* Where an asterisk appears in the tables, the division is required to be of steel or other equivalent material but is not required to be of "A" class standard. However, where a deck, except an open deck, is penetrated for the passage of electric cables, pipes and vent ducts, such penetrations should be made tight to prevent the passage of flame and smoke. Divisions between control stations (emergency generators) and open decks may have air intake openings without means for closure, unless a fixed gas fire-fighting system is fitted.
2.3.3.3 Continuous "B" class ceilings or linings, in association with the relevant decks or bulkheads, may be accepted as contributing, wholly or in part, to the required insulation and integrity of a division.
2.3.3.4 External boundaries which are required in regulation 11.2 to be of steel or other equivalent material may be pierced for the fitting of windows and sidescuttles provided that there is no requirement for such boundaries of cargo ships to have "A" class integrity. Similarly, in such boundaries which are not required to have "A" class integrity, doors may be constructed of materials which are to the satisfaction of the Administration.
2.3.3.5 Saunas shall comply with paragraph 2.2.3.4.
2.3.4 Protection of stairways and lift trunks in accommodation spaces, service spaces and control stations
2.3.4.1 Stairways which penetrate only a single deck shall be protected, at a minimum, at one level by at least "B-0" class divisions and self-closing doors. Lifts which penetrate only a single deck shall be surrounded by "A-0" class divisions with steel doors at both levels. Stairways and lift trunks which penetrate more than a single deck shall be surrounded by at least "A-0" class divisions and be protected by self-closing doors at all levels.
2.3.4.2 On ships having accommodation for 12 persons or less, where stairways penetrate more than a single deck and where there are at least two escape routes direct to the open deck at every accommodation level, the "A-0" requirements of paragraph 2.3.4.1 may be reduced to "B-0".
2.4 Tankers
2.4.1 Application
For tankers, only method IC as defined in paragraph 2.3.1.1 shall be used.
2.4.2 Fire integrity of bulkheads and decks
2.4.2.1 In lieu of paragraph 2.3 and in addition to complying with the specific provisions for fire integrity of bulkheads and decks of tankers, the minimum fire integrity of bulkheads and decks shall be as prescribed in tables 9.7 and 9.8.
2.4.2.2 The following requirements shall govern application of the tables:
- Tables 9.7 and 9.8 shall apply respectively to the bulkhead and decks separating adjacent spaces;
- For determining the appropriate fire integrity standards to be applied to divisions between adjacent spaces, such spaces are classified according to their fire risk as shown in categories (1) to (10) below. Where the contents and use of a space are such that there is a doubt as to its classification for the purpose of this regulation, or where it is possible to assign two or more classifications to a space, it shall be treated as a space within the relevant category having the most stringent boundary requirements. Smaller, enclosed areas within a space that have less than 30% communicating openings to that space are considered separate areas. The fire integrity of the boundary bulkheads and decks of such smaller spaces shall be as prescribed in tables 9.7 and 9.8. The title of each category is intended to be typical rather than restrictive. The number in parentheses preceding each category refers to the applicable column or row in the tables;
- Control stations
Spaces containing emergency sources of power and lighting.
Wheelhouse and chartroom.
Spaces containing the ship’s radio equipment.
Fire control stations.
Control room for propulsion machinery when located outside the machinery space.
Spaces containing centralized fire alarm equipment.
- Corridors
Corridors and lobbies.
- Accommodation spaces
Spaces as defined in regulation 3.1, excluding corridors.
- Stairways
Interior stairways, lifts, totally enclosed emergency escape trunks, andescalators (other than those wholly contained within the machinery spaces) and enclosures thereto.
In this connection, a stairway which is enclosed only at one level shall be regarded as part of the space from which it is not separated by a fire door.
- Service spaces (low risk)
Lockers and store-rooms not having provisions for the storage of flammable liquids and having areas less than 4 m2 and drying rooms and laundries.
- Machinery spaces of category A
Spaces as defined in regulation 3.31.
- Other machinery spaces
Electrical equipment rooms (auto-telephone exchange and airconditioning duct spaces).
Spaces as defined in regulation 3.30 excluding machinery spaces of category A.
- Cargo pump-rooms
Spaces containing cargo pumps and entrances and trunks to such spaces.
- Service spaces (high risk)
Galleys, pantries containing cooking appliances, saunas, paint lockers and store-rooms having areas of 4 m2 or more, spaces for the storage of flammable liquids and workshops other than those forming part of the machinery spaces.
- Open decks
Open deck spaces and enclosed promenades having little or no fire risk. To be considered in this category, enclosed promenades shall have no significant fire risk, meaning that furnishings shall be restricted to deck furniture. In addition, such spaces shall be naturally ventilated by permanent openings.
Air spaces (the space outside superstructures and deckhouses).
2.4.2.3 Continuous "B" class ceilings or linings, in association with the relevant decks or bulkheads, may be accepted as contributing, wholly or in part, to the required insulation and integrity of a division.
2.4.2.4 External boundaries which are required in regulation 11.2 to be of steel or other equivalent material may be pierced for the fitting of windows and sidescuttles provided that there is no requirement for such boundarie s of tankers to have "A" class integrity. Similarly, in such boundaries which are not required to have "A" class integrity, doors may be constructed of materials which are to the satisfaction of the Administration.
2.4.2.5 Exterior boundaries of superstructures and deckhouses enclosing accommodation and including any overhanging decks which support such accommodation, shall be constructed of steel and insulated to "A-60" standard for the whole of the portions which face the cargo area and on the outward sides for a distance of 3 m from the end boundary facing the cargo area. The distance of 3 m shall be measured horizontally and parallel to the middle line of the ship from the boundary which faces the cargo area at each deck level. In the case of the sides of those superstructures and deckhouses, such insulation shall be carried up to the underside of the deck of the navigation bridge.
2.4.2.6 Skylights to cargo pump-rooms shall be of steel, shall not contain any glass and shall be capable of being closed from outside the pump-room.
2.4.2.7 Construction and arrangement of saunas shall comply with paragraph 2.2.3.4.
Table 9.7 – Fire integrity of bulkheads separating adjacent spaces
Spaces | | (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | (10) |
Control stations | (1) | A-0c | A-0 | A-60 | A-0 | A-15 | A-60 | A-15 | A-60 | A-60 | * |
Corridors | (2) | | C | B-0 | B-0A-0a | B-0 | A-60 | A-0 | A-60 | A-0 | * |
Accommodationspaces | (3) | | | C | B-0A-0a | B-0 | A-60 | A-0 | A-60 | A-0 | * |
Stairways | (4) | | | | B-0A-0a | B-0A-0a | A-60 | A-0 | A-60 | A-0 | * |
Service spaces (low risk) | (5) | | | | | C | A-60 | A-0 | A-60 | A-0 | * |
Machinery spaces of category A | (6) | | | | | | * | A-0 | A-0d | A-60 | * |
Other machinery spaces | (7) | | | | | | | A-0b | A-0 | A-0 | * |
Cargo pump-rooms | (8) | | | | | | | | * | A-60 | * |
Service spaces (high risk) | (9) | | | | | | | | | A-0b | * |
Open decks | (10) | | | | | | | | | | - |
Table 9.8 – Fire integrity of decks separating adjacent spaces
| | (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | (10) |
Control stations | (1) | A-0 | A-0 | A-0 | A-0 | A-0 | A-60 | A-0 | - | A-0 | * |
Corridors | (2) | A-0 | * | * | A-0 | * | A-60 | A-0 | - | A-0 | * |
Accommodationspaces | (3) | A-60 | A-0 | * | A-0 | * | A-60 | A-0 | - | A-0 | * |
Stairways | (4) | A-0 | A-0 | A-0 | * | A-0 | A-60 | A-0 | - | A-0 | * |
Service spaces (low risk) | (5) | A-15 | A-0 | A-0 | A-0 | * | A-60 | A-0 | - | A-0 | * |
Machinery spaces of category A | (6) | A-60 | A-60 | A-60 | A-60 | A-60 | * | A-60e | A-0 | A-60 | * |
Other machinery spaces | (7) | A-15 | A-0 | A-0 | A-0 |