916 - Interpretations Of The International Code For The Application Of Fire Test Procedures (FTP Code) And Fire Test Procedures Referred To In The Code
Geldigheid:06-04-1999 t/m Status: Geldig vandaag

Dit onderwerp bevat de volgende rubrieken.

Ref.T4/4.01                                                                                                                    MSC/Circ.916

4June1999

 

 

1          TheMaritimeSafetyCommittee,atitsseventy-firstsession(19to28May1999),approved,with

aviewtoensuringuniformapplicationofthefiretestprovisionsoftheFTPCodecontainingvaguewording whichisopentodiverginginterpretations,theunifiedinterpretationspreparedbytheSub-Committeeon FireProtection,atitsforty-thirdsession,assetoutintheannex.

 

2          MemberGovernmentsareinvitedtousetheannexedinterpretationsasguidancewhenapplying relevantprovisionsoftheFTPCodeforthetestingofnewmaterialstestedonorafter21May1999,in ordertofulfilltherequirementsofthe1974SOLASConvention,andtobringtheseinterpretationstothe attentionofallpartiesconcerned.

 

 

 

 

 

***


Annex

INTERPRETATIONSOFTHEFTPCODEANDFIRETESTPROCEDURES REFERREDTOINTHECODE

 

 

 

Part2-Smokeandtoxicitytest

 

Paragrap h 2.6.2

 

NotonlytheFTIR(FourierTransformInfraredSpectrometer)methodbutalsoothermethodssuch

asGC/MS(GasChromatography/MassSpectrometer)whichcanproducetraceableresultscanbeusedfor thegasanalysis.

 

Part3-Testfor"A","B",and"F"classdivisions

 

Paragrap h 2. 1 (paragrap h 2.6.2. 2 o f resolutio n A.754(18))

 

"B" class doors should be fire tested in B class steel bulkheads of dimensions as stated in paragraph2.4.1ofresolutionA.754(18),otherwiseapprovalshouldbelimitedtothetypeofconstruction

inwhichthedoorwastested."

 

Paragrap h 3.1

 

The calcium silicate board described as a dummy specimen specified in paragraph 3.3 of resolutionA.653(16)shouldbeusedasastandardsubstrateforadhesives.

 

Paragrap h 1. 7 o f resolutio n A.754(18)

 

"B" class constructionsshouldbetestedwithoutfinishes.   Forconstructionswherethisisnot possible,finishesshouldbeincludedinthenon-combustibilitytestoftheconstruction.

 

Paragrap h 1. 2 o f resolutio n A.754(18)

 

Thethicknessofinsulationonthestiffenersneednotbesameasthatofthesteelplate.

 

Paragrap h 4. 1 o f Appendi x A.II I an d paragrap h 4. 1 o f Appendi x A.I V o f resolutio n A.754(18)

 

Penetrationsandtransitsshouldmeetbothintegrityandinsulationcriteria.