Onderwerp: Bezoek-historie

1437 UI of SOLAS reg. II-2/21.4
Geldigheid:31-05-2012 t/m Versie:vergelijk
Vergelijk versie 2 met:
Status: Geldig vandaag

Dit onderwerp bevat de volgende rubrieken.

Annex

Annex

(To be used in conjunction with the interim explanatory notes for the assessment of passenger ship systems' capabilities after a fire or flooding casualty (MSC.1/Circ.1369))


Regulation II-2/21.4 – Fire and flooding casualty, pipes and vent ducts
All pipes and vent ducts passing through (not serving) a compartment affected by a flooding casualty are considered to remain operational provided they, together with relevant fittings, are capable of withstanding the head of water expected at their location.

Regulation II-2/21.4 – Fire and flooding casualty, electrical cables
Electrical cables complying with standard IEC 60092-359 may be considered to remain operational in a space affected by a flooding casualty, provided they have no connections, no joints, no equipment connected to them, etc., within such space or such connections, joints and devices have a degree of protection IPX8 in accordance with standard IEC 60529 (head of water expected at their location for a period not inferior to that estimated for the safe return to port).

Regulation II-2/21.4.4 – Systems for fill, transfer and service of fuel oil
Systems for internal fill, transfer and service of:

  1. fuel;

  2. other flammable hydrocarbons; or

  3. any fluid that may be flammable or dangerous if heated to a very high temperature  both within the pipe and ongoing through pumps, orifices or other equipment),

should be established as being capable of remaining operational when crossing flooded watertight compartments, considering in particular consequences of low seawater temperature on liquids behaviour.

Regulation II-2/21.4.6 – External communications

  1. Portable radiocommunication equipment might be accepted; and

  2. charging capability for any portable devices should be available in more than one main vertical zone (MVZ).
Naar boven